Greenheck CRD-1WT Installation, Operation And Maintenance Instructions
Greenheck CRD-1WT Installation, Operation And Maintenance Instructions

Greenheck CRD-1WT Installation, Operation And Maintenance Instructions

Ceiling radiation damper for wood truss application

Advertisement

Quick Links

®
Installation, Operation and Maintenance Instructions
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100°F (38°C).
Safety Warning:
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
These instructions describe the installation of a CRD-1WT in designs: M508 and P554 as detailed in the UL Fire
Resistance Directory.
2
1
Flooring Systems
2
Wood Truss
3
Air Ducts
4
CRD-1WT assembly
5
Mounting Angle
6
Resilient Channel
7
Gypsum Board
8
Grille (not supplied)
9
Finishing System
(not shown)
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the
job is complete.
®
1
5
7
Document Number 474094
Ceiling Radiation Damper for
Wood Truss Application
CRD-1WT Dampers are intended for installation in
accordance with ceiling radiation damper requirements
established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
"UL CLASSIFIED (see complete marking on
product)"
UL Standard 555C (Classification #R13446)
3
4
CRD-1WT
6
8
Figure 1

Advertisement

loading

Summary of Contents for Greenheck CRD-1WT

  • Page 1 Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. These instructions describe the installation of a CRD-1WT in designs: M508 and P554 as detailed in the UL Fire Resistance Directory. Flooring Systems Wood Truss...
  • Page 2: Installation

    Installation Guidelines 1) CRD’s are shipped from the factory with the blades in the closed position. The fusible link must be installed at the time of installation such that the blades are held open as shown in Figure 2. 2) Fasteners (screws, bolts, rivet, etc.) used for installation must not interfere with blade operation.
  • Page 3 1. Damper 2. Mounting Angle 3. Plaster Flange 4. Gypsum Board 5. Grille 6. RC Channel 7. Duct Board Plenum Figure 5: Grille Mount with Duct Board Plenum 1. Damper 2. Mounting Angle 3. Plaster Flange 4. Gypsum Board 5. Duct 6.
  • Page 4 CRD-1WT Duct Mount CRD-1WT Grille Mount Figure 8 Fabrication of Fiberglass Ductboard Plenum for CRD-1WT 1. Fiberglass ductboard shall be a minmum of 1 inch 5. The plenum duct collars shall be minimum of 30 (25mm) thick UL181 Listed and have a minmum ga.
  • Page 5: Damper Maintenance

    Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with: Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warrantees can be located on greenheck.com within the prod- uct area tabs and listed in the Library under Warrantees.