NX-320E Remote Power Supply
Installation Manual

Wiring

When you connect the unit, do the following:
For UL commercial fire installations, use at least 18 AWG for all field wiring. We do not recommend
shielded wire.
Use a 16.5 VAC 50 VA / 120 V, 60 Hz hard-wired transformer (GE Security #T-0002).
Do not connect multiple power supply modules in a series (cascaded). The board is wrapped in bubble wrap.
Unwrap it so you can orient yourself as you review Figure 2.
Figure 2. Board connections
LED 1
LED 2
LED 4
In terminals
Wiring requirements
Use Table 1 to calculate your wiring requirements. We do not recommend shielded wire. For UL Commercial
Fire installations, a minimum of 18 AWG must be used for all field-wiring applications.
Table 1.
Wiring requirements
Length (in ft.)
400
500
1000
2000
2500
Battery wires
LED 3
DIP switch block
Wire gauge (when connected to NetworX panel)
24
24
24
22
20
Expansion terminals