7SR18 Description Of Operation
3.5.2
Instantaneous Measured Earth Fault Protection (50G)
Up to four instantaneous derived earth fault elements are provided in the relay (depending upon variant): -
Each instantaneous element has independent settings for pick-up current 50G-n Setting and a follower time
delay 50G-n Delay. The instantaneous elements have transient free operation.
Operation of the instantaneous measured earth fault elements can be inhibited from:
Inhibit 50G-n
79 E/F Inst Trips: 51N-n
50-n Inrush Action: Block
50G-n VTSAction: Inhibit
Figure 3.5.2-1 Logic Diagram: Measured Instantaneous Earth-fault Element
Unrestricted Page 42 of 78
50G-1, 50G-2, 50G-3 & 50G-4
A binary or virtual input.
When 'delayed' trips only are allowed in the auto-reclose sequence
(79 E/F Prot'n Trip n = Delayed).
Operation of the inrush current detector function.
Operation of the VT Supervision function