Time Delayed Derived Earth Fault Protection (51N); Figure 3.4.3-1 Logic Diagram: Derived Time Delayed Earth Fault Element - Siemens 7SR18 Solkor Manual

Reyrolle protection devices, energy management, line differential relay
Table of Contents

Advertisement

7SR18 Description Of Operation
3.4.3

Time Delayed Derived Earth Fault Protection (51N)

Up to four time-delayed derived earth fault elements are provided in the relay (depending upon variant): -
51N-n Setting sets the pick-up current level.
A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is
selected from IEC and ANSI curves using 51N-n Char. A time multiplier is applied to the characteristic curves
using the 51N-n Time Mult setting. Alternatively, a definite time lag delay (DTL) can be chosen using 51N-n
Char. When definite time lag (DTL) is selected the time multiplier is not applied and the 51N-n Delay (DTL)
setting is used instead.
The 51-n Reset setting can apply a definite time delayed reset, or when the operation is configured as an IEC or
ANSI or user characteristic if the reset is selected as IEC/ANSI (DECAYING) reset the associated reset curve will
be used. The reset mode is significant where the characteristic has reset before issuing a trip output – see
'Applications Guide'
A minimum operate time for the characteristic can be set using the 51N-n Min. Operate Time setting.
A fixed additional operate time can be added to the characteristic using the 51N-n Follower DTL setting.
Operation of the time delayed earth fault elements can be inhibited from: -
Inhibit 51N-n
50-n Inrush Action: Block

Figure 3.4.3-1 Logic Diagram: Derived Time Delayed Earth Fault Element

Unrestricted Page 40 of 78
51N-1, 51N-2, 51N-3 & 51N-4
A binary or virtual input.
Operation of the inrush current detector function.
©2018 Siemens Protection Devices Limited

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents