1MRK 511 440-UEN A
DO name
DO type
Pos
c_dDPC
SwOpCap
f_dINS
SwTyp
g_dINS
BlkUpd
v1_dSPC
Switchgear control unit SAM600-IO Version 2.2 IEC
Communication protocol manual
DA name
FC
q
ST
t
ST
subEna
SV
subVal
SV
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
Oper.ctlVal
CO
Oper.origin.orCat
CO
Oper.origin.orIdent
CO
Oper.ctlNum
CO
Oper.T
CO
Oper.Test
CO
Oper.Check
CO
stVal
ST
q
ST
t
ST
T
Signal
-
POSITION
-
POSITION
-
-
-
-
-
SWOPCAP
-
SWOPCAP
-
SWOPCAP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
UPD_BLKD
-
UPD_BLKD
-
UPD_BLKD
Section 7
Logical node data model
Mon/C
Description
md
Mon
Quality: Apparatus position
indication
Mon
Timestamp: Apparatus position
indication
-
Substitute enable
-
Substituted double position value
Mon
Switch operating capability 1 =
None, 2 = O, 3 = C, 4 = O and C
Mon
Quality: Switch operating
capability 1 = None, 2 = O, 3 = C,
4 = O and C
Mon
Timestamp: Switch operating
capability 1 = None, 2 = O, 3 = C,
4 = O and C
Mon
1=LoadBreak,2=Disconnector,
3=EarthSw,
4=HighSpeedEarthSw
Mon
Quality: 1=LoadBreak,
2=Disconnector,3=EarthSw,
4=HighSpeedEarthSw
Mon
Timestamp: 1=LoadBreak,
2=Disconnector,3=EarthSw,
4=HighSpeedEarthSw
Cmd
Special block command value
Cmd
Special block command value
Cmd
Special block command value
Cmd
Special block command value
Cmd
Special block command value
Cmd
Special block command value
Cmd
Special block command value
Mon
Update of position indication is
blocked
Mon
Quality: Update of position
indication is blocked
Mon
Timestamp: Update of position
indication is blocked