ABB SAM600-IO Protocol Manual page 77

Switchgear control unit
Hide thumbs Also See for SAM600-IO:
Table of Contents

Advertisement

1MRK 511 440-UEN A
DO name
DO type
ClsAlm
v1_dSPS
OpNumAlm
v1_dSPS
OpNumLO
v1_dSPS
APwrAlm
v1_dSPS
APwrLO
v1_dSPS
LonTmAlm
v1_dSPS
SprChaAlm
v1_dSPS
PosOpn
v1_dSPS
Table continues on next page
Switchgear control unit SAM600-IO Version 2.2 IEC
Communication protocol manual
DA name
FC
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
T
Signal
-
TRVTCLAL
-
TRVTCLAL
-
OPERALM
-
OPERALM
-
OPERALM
-
OPERLO
-
OPERLO
-
OPERLO
-
IPOWALPH
-
IPOWALPH
-
IPOWALPH
-
IPOWLOPH
-
IPOWLOPH
-
IPOWLOPH
-
MONALM
-
MONALM
-
MONALM
-
SPCHALM
-
SPCHALM
-
SPCHALM
-
OPENPOS
-
OPENPOS
Section 7
Logical node data model
Mon/C
Description
md
Mon
Quality: CB close travel time
exceeded set value
Mon
Timestamp: CB close travel time
exceeded set value
Mon
Number of CB operations
exceeds alarm limit
Mon
Quality: Number of CB operations
exceeds alarm limit
Mon
Timestamp: Number of CB
operations exceeds alarm limit
Mon
Number of CB operations
exceeds lockout limit
Mon
Quality: Number of CB operations
exceeds lockout limit
Mon
Timestamp: Number of CB
operations exceeds lockout limit
Mon
Accum I^CurrExponent integr
over CB open travel time exceeds
alarm limit
Mon
Quality: Accum I^CurrExponent
integr over CB open travel time
exceeds alarm limit
Mon
Timestamp: Accum
I^CurrExponent integr over CB
open travel time exceeds alarm
limit
Mon
Accum I^CurrExponent integr
over CB open travel time exceeds
lockout limit
Mon
Quality: Accum I^CurrExponent
integr over CB open travel time
exceeds lockout limit
Mon
Timestamp: Accum
I^CurrExponent integr over CB
open travel time exceeds lockout
limit
Mon
CB 'not operated for long time'
alarm
Mon
Quality: CB 'not operated for long
time' alarm
Mon
Timestamp: CB 'not operated for
long time' alarm
Mon
Spring charging time has crossed
the set value
Mon
Quality: Spring charging time has
crossed the set value
Mon
Timestamp: Spring charging time
has crossed the set value
Mon
CB is in open position
Mon
Quality: CB is in open position
71

Advertisement

Table of Contents
loading

Table of Contents