Greenheck CRD-501 Installation, Operation And Maintenance Instructions
Greenheck CRD-501 Installation, Operation And Maintenance Instructions

Greenheck CRD-501 Installation, Operation And Maintenance Instructions

Ceiling radiation damper

Advertisement

Quick Links

®
Installation, Operation and Maintenance Instructions
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100°F (38°C).

Table of Contents

Ceiling Radiation Damper Application ............................................................................................................... 2
Damper Supported by a Ceiling Grid System ................................................................................................. 2-3
Damper Supported from Ductwork Above ...................................................................................................... 4-5
Damper Supported Directly From Structure.................................................................................................... 5-8
Connection and Operation of Thermostat .......................................................................................................... 8
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when
the job is complete.
..................................................................................................................................... 3
.......................................... .................................................................3
............................................................................................................. 4
............................................ .................................................................5
................................................................................................ 6
............................. .................................................................6-7
Document Number 475063
Ceiling Radiation Damper
"UL CLASSIFIED (see complete marking on
product)"
"UL CLASSIFIED to Canadian safety standards
(see complete marking on product)"
Standard 555C (Listing #R13317)
Standard 555S (Listing #R13317)
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit
caused by incorrect field wiring. To avoid causing death
or serious bodily harm to building occupants, follow all
instructions carefully. Dampers must close completely to
preserve the integrity of the fire smoke separation.
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specifications.
............................................................................................ 7
............................................................................................. 8
Installation Instructions
Safety Warning:
Safety Caution!
Electrical Guidelines
CRD-501

Advertisement

loading

Summary of Contents for Greenheck CRD-501

  • Page 1: Table Of Contents

    Connection and Operation of Thermostat ......................8 Due to continuing research, Greenheck reserves the right to change specifications without notice. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when...
  • Page 2: Ceiling Radiation Damper Application

    3. Ceiling Penetrations: Ceiling penetration should Bars (if any). be located within ceiling tiles or panels without 6. Thermostat: The CRD-501 is shipped from the necessitating cuts in the ceiling suspension main factory with the blades closed. The CRD-501 is runners or cross tees.
  • Page 3 Dampers Supported By A Ceiling Grid System Lay-In Diffuser Applications it shall be fastened to the diffuser neck with a steel Lay-In Diffuser clamp or #16 SWG minimum wire. NOTE: (1) The flexible air duct shall not rest on the back surface of the ceiling grid or panels (provide a minimum grid system.
  • Page 4: Damper Supported From Ductwork Above

    Dampers Supported From Ductwork Above A Note About Support all required support for ceiling damper and air inlet When main ducts are supported by 16 ga. x 1½ in. or outlet devices. Air device flange must overlap the (1.5mm x 38mm) steel channels (with 9/16 in. [14mm] ceiling membrane by a minimum of 1 inch (25.4mm).
  • Page 5 Dampers Supported From Ductwork Above cont... Recess Mounted Air Inlet Or Outlet Devices 1. Ceiling radiation damper may be connected directly to the air device neck and then the duct ceiling damper (i.e. if the radiation damper is 12 in. drop connected to the damper (see Detail B, diameter [305mm] (nominal), the ceiling membrane Figure 4).
  • Page 6: Damper Supported Directly From Structure

    Dampers Supported Directly From Structure A Note About Support Ceiling radiation dampers and air inlet or outlet devices minimum flanges (2 required per damper on opposite may also be supported directly from the structure sides). Air device flange must overlap the ceiling above using one or more of the methods described in membrane by a minimum of one inch.
  • Page 7 Dampers Supported Directly From Structure cont..Ducted Recess Mounted Air Inlet Or Outlet Devices neck, and steel duct drop (See Page 2, Paragraph 4) may be satisfied as follows: ceiling radiation damper is 12 in. diameter [305mm] (nominal), the ceiling membrane opening is larger 1.
  • Page 8 Dampers Supported Directly From Structure cont..Detail C Detail D All hanger wires Non - Ferrous must be vertical Device (not splayed)! Detail B Ceiling Radiation Damper 6 3/4 in. (171mm) maximum (Inlet or Outlet) Ferrous Detail E Device Detail A Device Non - Ferrous Figure 7...
  • Page 9: Connection And Operation Of Thermostat

    212° F (optional primary sensor) Figure 9 Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.