To avoid injury to persons, damage to property or the environment, the following
warning notes must be observed!
Do not to open, interfere with or modify the unit!
All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
Before making any wiring changes in the connection area, completely isolate the
plant from mains supply (all-polar disconnection). Ensure that the plant cannot be
inadvertently switched on again and that it is indeed dead. If not observed, there is
a risk of electric shock hazard
Ensure protection against electric shock hazard by providing adequate protection
for the burner control's connection terminals
Check the connecting lines of the air pressure switch for short-circuits (connection
terminals 3, 6 and 11)
Press the lockout reset button / operation button of LME... or the AGK20... lockout
reset button extension only manually (applying a force of no more than 10 N) with-
out using any tools or pointed objects
Fall or shock can adversely affect the safety functions. Such units must not be put
into operation, even if they do not exhibit any damage
Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state and make the safety checks as
described in «Commissioning notes»
When used in connection with actuators, there is no position feedback signal from
the actuator to the burner control
When used in connection with actuators, the requirements of applicable norms and
regulations must be observed
The running times of the actuators must match the burner control's program. An
additional safety check of the burner control together with the actuators is required
When substituting burner controls type LGB... or LMG... by LME..., the AGQ1... or
AGQ2... ancillary unit must be replaced by the AGQ3...A27
Ensure that the relevant national safety regulations are complied with