12. SERVICE PROCEDURES
3)
Checking the Electrical Parts
1
Power transformer ...........................Indoor unit
• Primary 230-208 V ; Measure the resistance between two WHT lead wire terminals
• Secondary 19 V
2
Power transformer (TR) ................. Outdoor unit
• Primary 230-208 V ; Measure the resistance between two WHT lead wire terminals
• Secondary 19 V
Indoor fan motor (FMI) ............... Indoor unit
3
• Measure the resistance between each terminal of the socket connected to the
indoor fan motor.
Outdoor fan motor (FMO) ........... Outdoor unit
4
• Measure the resistance in the same manner as explained above 2 .
5
Motor capacitor ............ Both in indoor and outdoor unit
• Remove the lead wires from the
capacitor terminals, and then place a
probe on the capacitor terminals as
shown in Fig. 21. Observe the deflec-
tion of the pointer, setting the resis-
tance measuring range of the multim-
eter to the maximum value.
• The capacitor is "good" if the pointer
bounces to a great extent and then
gradually returns to its original posi-
tion.
NOTE
The range of deflection and the deflection
time differ according to the capacity of the
capacitor.
of socket connected to power transformer.
; Measure the resistance between two BRN lead wires.
of socket jointed to power transformer.
; Measure the resistance between two BRN lead wires.
– 53 –
*Measure the coil resistance.
*Measure the coil resistance.
*Measure the coil resistance.
*Measure the coil resistance.
Compressor motor
capacitor
Fig. 21
Multimeter
Fan motor
capacitor
1041_X_S
SM830092