Terminal Block Layouts; Triac Output Specifications And Example Of External Wiring; External Wiring Of Transistor Output; Cautions In External Wiring - Mitsubishi Electric FX3U-32MR/ES User Manual

Fx3u series; fx2n series
Table of Contents

Advertisement

Item
Specification
5 s or less/10 mA
Y000 to
Y002
or more (5 to 24 V DC)
Main unit
OFF
Y003 or
0.2 ms or less/200 mA
more
or more (at 24 V DC)
ON
Input/output extension
0.2 ms or less/200 mA
*
units/blocks (
7)
or more (at 24 V DC)
Response
time
5 s or less/10 mA
Y000 to
Y002
or more (5 to 24 V DC)
Main unit
ON
Y003 or
0.2 ms or less/200 mA
more
or more (at 24 V DC)
OFF
Input/output extension
0.2 ms or less/200 mA
*
units/blocks (
7)
or more (at 24 V DC)
Output circuit insulation
Photocoupler insulation
LED on panel lights when
Output operation display
photocoupler is driven.
*
(
1) The total load current of resistance loads per common
terminal should be the following value.
-
1 output point/common terminal: 0.5 A or less
-
4 output point/common terminal: 0.8 A or less
-
8 output point/common terminal: 1.6 A or less
As for the number of outputs per common terminal, refer to
"Chapter 4 interpretation of partition" and the following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
(
*
2) The total load current of resistance loads per common
terminal should be the following value.
-
4 output points/common terminal: 2 A or less
As for the number of outputs per common terminal, refer to the
following manual.
Refer to FX
3U
Series User's Manual - Hardware Edition.
*
(
3) The total load current of resistance loads per common
terminal should be the following value.
-
16 output point/common terminal: 1.6 A or less
As for the number of outputs per common terminal, refer to the
following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
*
(
4) The total of inductive loads per common terminal should be
the following value.
-
1 output point/common terminal: 12 W or less/24 V DC
-
4 output points/common terminal: 19.2 W or less/24 V DC
-
8 output points/common terminal: 38.4 W or less/24 V DC
As for the number of outputs per common terminal, refer to
"Chapter 4 interpretation of partition" and the following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
(
*
5) The total of inductive loads per common terminal should be
the following value.
-
4 output points/common terminal: 48 W or less/24 V DC
As for the number of outputs per common terminal, refer to the
following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
*
(
6) The total of inductive loads per common terminal should be
the following value.
-
16 output points/common terminal: 38.4 W or less
As for the number of outputs per common terminal, refer to the
following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
*
(
7) The response time is as follows in the FX
-8EYT-H.
2N
-
OFFON: 0.2 ms or less/1 A
-
ONOFF: 0.4 ms or less/1 A
3.6.2

External wiring of transistor output

1. External wiring of sink output type
Load
Y000
Y001
Fuse
24 V DC
COM1
Load
Y004
Y005
Fuse
24 V DC
COM2
PLC
2. External wiring of source output type
Load
Y000
Y001
Fuse
24 V DC
+V0
Load
Y004
Y005
Fuse
24 V DC
+V1
PLC
3.6.3

Cautions in external wiring

For cautions in external wiring, refer to the following manual.

Refer to FX
Series User's Manual - Hardware Edition.
3U
Protection circuit for load short-circuits
A short-circuit at a load connected to an output terminal could cause
burnout at the output element or the PCB. To prevent this, a
protection fuse should be inserted at the output.
Use a load power supply capacity that is at least 2 times larger than
the total rated fuse capacity.
Contact protection circuit for inductive loads
When an inductive load is connected, connect a diode (for
commutation) in parallel with the load as necessary.
The diode (for commutation) must comply with the following
specifications.
Item
Guide
Reverse voltage
5 to 10 times of the load voltage
Forward current
Load current or more
Interlock
Loads, such as contactors for normal and reverse rotations, that
must not be turned on simultaneously should have an interlock in the
PLC program and an external interlock.
3.7
Triac output specifications and example of
external wiring
As for the details of the triac output specifications and external
wiring, refer to the following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
3.7.1
Triac output specifications
Item
Specification
FX
-32MS/ES,
3U
Number
FX
-16EYS,
16 points
2N
of output
FX
2N
-32ES
points
FX
-64MS/ES
32 points
3U
Refer to FX
Series
3U
Output connecting type
User's Manual - Hardware
Edition
Output form
Triac (SSR)
External power supply
85 to 242 V AC
*
0.3 A/point (
1)
Resistance load
Max. load
15 VA/100 V AC,
Inductive load
30 VA/200 V AC
0.4 VA/100 V AC,
Min. load
1.6 VA/200 V AC
1 mA/100 V AC,
Open circuit leakage current
2 mA/200 V AC
OFFON
1 ms or less
Response
time
ONOFF
10 ms or less
Output circuit insulation
Photo-thyristor insulation
LED on panel lights when
Output operation display
photo-thyristor is driven.
*
(
1) The total load current of resistance loads per common
terminal should be the following value.
-
4 output points/common terminal: 0.8 A or less
-
8 output points/common terminal: 0.8 A or less
As for the number of outputs per common terminal, refer to
"Chapter 4 interpretation of partition" and the following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
3.7.2
External wiring of triac output
Load
Y000
Y001
AC power
Fuse
supply
U
COM1
Load
Y004
Y005
AC power
Fuse
supply
U
COM2
PLC
3.7.3
Cautions in external wiring
For cautions in external wiring, refer to the following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
Protection circuit for load short-circuits
A short-circuit at a load connected to an output terminal could cause
burnout at the output element or the PCB. To prevent this, a
protection fuse should be inserted at the output.
Micro current load
The PLC's internal Triac output circuit is equipped with a turn-off C-R
absorber. When connecting a very low current load of "0.4 VA/100 V
AC or less, or 1.6 VA/200 V AC or less", please connect a surge
absorber parallel to the load.
Select the rated voltage of a surge absorber that is suitable for the
load being used. Refer to the table below for other specifications.
Item
Guide
Approx. 0.1 F
Static electricity capacity
Approx. 100 to 200 
Resistance value
Interlock
Loads, such as contactors for normal and reverse rotations, that
must not be turned on simultaneously should have an interlock in the
PLC program and an external interlock.
4.

Terminal block layouts

For details on the terminal block layout, refer to the following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
Interpretation of partition
The partition of the output terminals (see following figure) indicates
the range of the output connected to the same common.
Example: FX
-48MT/ES
3U
Output terminal
Y0
Y2
Y4
COM1
Y1
Y3
COM2
Partition
This manual confers no industrial property rights or any rights of any
other kind, nor does it confer any patent licenses. Mitsubishi Electric
Corporation cannot be held responsible for any problems involving
industrial property rights which may occur as a result of using the
contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found
not to be the cause of Mitsubishi; opportunity loss or lost profits
caused by faults in the Mitsubishi products; damage, secondary
damage, accident compensation caused by special factors
unpredictable by Mitsubishi; damages to products other than
Mitsubishi products; and to other duties.