External Wiring Of Transistor Output; Triac Output Specifications; External Wiring Of Triac Output; Terminal Block Layouts - Mitsubishi Electric FX3U-128M series Hardware Manual

Melsec-f fx3u series
Hide thumbs Also See for FX3U-128M series:
Table of Contents

Advertisement

3.6.2

External wiring of transistor output

1. External wiring of sink output type
Load
Y000
Y001
Fuse
24 V DC
COM1
Load
Y004
Y005
Fuse
24 V DC
COM2
PLC
2. External wiring of source output type
Load
Y000
Y001
Fuse
24 V DC
+V0
Load
Y004
Y005
Fuse
24 V DC
+V1
PLC
3.6.3
Cautions in external wiring
For cautions in external wiring, refer to the following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
Protection circuit for load short-circuits
A short-circuit at a load connected to an output terminal could cause
burnout at the output element or the PCB. To prevent this, a
protection fuse should be inserted at the output.
Use a load power supply capacity that is at least 2 times larger than
the total rated fuse capacity.
Contact protection circuit for inductive loads
When an inductive load is connected, connect a diode (for
commutation) in parallel with the load as necessary.
The diode (for commutation) must comply with the following
specifications.
Item
Guide
Reverse voltage
5 to 10 times of the load voltage
Forward current
Load current or more
Interlock
Loads, such as contactors for normal and reverse rotations, that
must not be turned on simultaneously should have an interlock in the
PLC program and an external interlock.
3.7
Triac output specifications and example of
external wiring
As for the details of the triac output specifications and external
wiring, refer to the following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
3.7.1

Triac output specifications

Item
Specification
FX
-32MS/ES,
3U
Number
FX
-16EYS,
16 points
2N
of output
FX
-32ES
2N
points
FX
-64MS/ES
32 points
3U
Refer to FX
Series
3U
Output connecting type
User's Manual - Hardware
Edition
Output form
Triac (SSR)
External power supply
85 to 242 V AC
*
0.3 A/point (
1)
Resistance load
Max. load
15 VA/100 V AC,
Inductive load
30 VA/200 V AC
0.4 VA/100 V AC,
Min. load
1.6 VA/200 V AC
1 mA/100 V AC,
Open circuit leakage current
2 mA/200 V AC
OFFON
1 ms or less
Response
time
ONOFF
10 ms or less
Output circuit insulation
Photo-thyristor insulation
LED on panel lights when
Output operation display
photo-thyristor is driven.
*
(
1) The total load current of resistance loads per common
terminal should be the following value.
-
4 output points/common terminal: 0.8 A or less
-
8 output points/common terminal: 0.8 A or less
As for the number of outputs per common terminal, refer to
"Chapter 4 interpretation of partition" and the following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
3.7.2

External wiring of triac output

Load
Y000
Y001
AC power
Fuse
supply
U
COM1
Load
Y004
Y005
AC power
Fuse
supply
U
COM2
PLC
3.7.3
Cautions in external wiring
For cautions in external wiring, refer to the following manual.
Refer to FX
3U
Series User's Manual - Hardware Edition.
Protection circuit for load short-circuits
A short-circuit at a load connected to an output terminal could cause
burnout at the output element or the PCB. To prevent this, a
protection fuse should be inserted at the output.
Micro current load
The PLC's internal Triac output circuit is equipped with a turn-off C-R
absorber. When connecting a very low current load of "0.4 VA/100 V
AC or less, or 1.6 VA/200 V AC or less", please connect a surge
absorber parallel to the load.
Select the rated voltage of a surge absorber that is suitable for the
load being used. Refer to the table below for other specifications.
Item
Guide
Approx. 0.1 F
Static electricity capacity
Resistance value
Approx. 100 to 200 
Interlock
Loads, such as contactors for normal and reverse rotations, that
must not be turned on simultaneously should have an interlock in the
PLC program and an external interlock.
4.

Terminal block layouts

For details on the terminal block layout, refer to the following manual.
Refer to FX
Series User's Manual - Hardware Edition.
3U
Interpretation of partition
The partition of the output terminals (see following figure) indicates
the range of the output connected to the same common.
Example: FX
-48MT/ES
3U
Output terminal
Y0
Y2
Y4
COM1
Y1
Y3
COM2
Partition
This manual confers no industrial property rights or any rights of any
other kind, nor does it confer any patent licenses. Mitsubishi Electric
Corporation cannot be held responsible for any problems involving
industrial property rights which may occur as a result of using the
contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for
compensation to:
(1) Damages caused by any cause found not to be the responsibility
of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of
Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable
or not, compensation for accidents, and compensation for damages
to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up
test run and other tasks.

For safe use

This product has been manufactured as a general-purpose part for
general industries, and has not been designed or manufactured to
be incorporated in a device or system used in purposes related to
human life.
Before using the product for special purposes such as nuclear
power, electric power, aerospace, medicine or passenger
movement vehicles, consult with Mitsubishi Electric.
This product has been manufactured under strict quality control.
However when installing the product where major accidents or
losses could occur if the product fails, install appropriate backup or
failsafe functions in the system.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI,
CHIYODA-KU, TOKYO 100-8310, JAPAN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3u-16m seriesFx2n-48e seriesFx2n-8e seriesFx2n-16e seriesFx2n-32e series

Table of Contents