Foundation
KG 40-100:
Insulation strips
on-site
Unit connection
6

Installation information

A level, horizontal and load-bearing surface is required to site and install the
Please note
units and unit components.
Base frames must be levelled horizontally; foundation plinths must also be
level and horizontal.
The entire lower unit frame must sit on the foundation; point loads are not
permissible.
To prevent structure-borne noise being transmitted from air handling units to
the building, insert a permanently flexible intermediate layer between the plinth/
foundation and the unit/base frame. This intermediate layer should ideally take
the form of insulation strips, fitted lengthwise below the unit frame sections.
Base frames are delivered either securely fitted to the unit or loose (in advance).
If the base frame is delivered in advance, replace the screw with the
stud provided.
Loose base frames are delivered in individual sections and must be assembled
on site in accordance with the instructions supplied with the base frame, levelled,
and secured to the plinth.
If units are delivered in sections with the base frame fitted, the base frame and
unit will be split at the same points.
When being positioned on the base frame or foundation plinth, align the units
Washer
in such a way that a gap of approximately 10 mm is maintained between the
base frame or foundation plinth and the drip guard.
Screw
When installation is complete, securely fix the air handling units to the base
Clip
frame or foundation plinth using the clips provided.
Stud
Drip guard
Base frame
For units with a scrubber, use a base frame or foundation plinth because the
scrubber base is lower than the remaining unit base. The required height of
this base frame depends on the type of scrubber and is determined individually
when designing the unit.
The connection is made using M6 screws and spacer clips, for which holes
are provided at the appropriate points in the cubes. All small parts required
for assembly, plus loose accessories, are supplied in a unit with an inspection
door (preferably a fan section). This unit will be marked with a label reading
"Accessories inside unit".
In order to completely waterproof the unit, apply the self-adhesive sealing tape
supplied with the unit to one side before the cubes are joined.