Equipment installation
Base frame / foundation
base
Internal unit base frame
3064058_201610
Installation instructions
Appliances for weatherproof installation must not take on any static load or act as a
Note
substitute for the roof of the building.
When assembling and installing combined ventilation and extract appliances with heat
Note
recovery (KGXD, RWT), observe the correct sequence of assembly and installation
(see diagram). For this, one complete appliance train should always be assembled/
installed completely. The second appliance should then be installed from the heat
recovery onwards.
This offers the most effective prevention of alignment errors and installation inaccuracies.
Appliance example - top view:
When installing high or perhaps smaller appliance components (e.g. RWT, RWT duct
components or standing appliance layouts with several components above each
other), secure these during assembly/installation against tipping until they are finally
connected to other components that ensure that tipping is prevented.
Requires permanent securing against tipping over.
Note
WOLF internal unit base frames (suitable only for internal installation) are always sup-
plied loose (in advance).
Base frames delivered loose are knocked down for shipping and must be assembled,
aligned and secured to the base on site in accordance with the instructions enclosed
with the base frame.
AHUW TE
Risk of tipping
AHU TE
9