Installation and Maintenance Instructions
Air handling unit KG Standard
(Translation of the original)
Wolf GmbH • Postfach 1380 • D-84048 Mainburg • Tel.+49 ( 0) 8751/74-0 • Fax +49 (0) 8751/74-1600 • Internet: www.wolf-heiztechnik.de
GB
Part no.: 3040530_201503
Subject to modifications

Advertisement

Table of Contents
loading

Summary of Contents for Wolf KG Standard

  • Page 1 Installation and Maintenance Instructions Air handling unit KG Standard (Translation of the original) Wolf GmbH • Postfach 1380 • D-84048 Mainburg • Tel.+49 ( 0) 8751/74-0 • Fax +49 (0) 8751/74-1600 • Internet: www.wolf-heiztechnik.de Part no.: 3040530_201503 Subject to modifications...
  • Page 2: Table Of Contents

    Electrical connection............11-13 Commissioning ..............14-17 Maintenance ............... 18-20 Frost protection................ 20 Checklist .................. 21 Notes .................. 22-23 Order-specific appliance details, such as weights, dimensions, noise data, spare parts, energy data, etc., can be found in the order datasheets. Original WOLF spare parts can be obtained quickly by faxing +49 (0) 8751/74-1574, and stating the order number (on the type plate). 3040530_201503...
  • Page 3: Reference Symbols / Safety Instructions

    - Wolf air handling units KG Standard". The installation instructions should be considered an integral part of the unit supplied, and should be retained in an easily accessible location. Failure to observe the installation and operating instructions voids any Wolf warranty. Reference symbols The following symbols are used in these installation and maintenance instructions.
  • Page 4: Standards

    Standards Standards The following standards and regulations apply to air handling units in the KG 15-100 Standard series: - Machinery Directive 2006/42/EC - Low Voltage Directive 2006/95/EC - EMC Directive 2004/108/EC - Pressure Equipment Directive 97/23/EC - DIN EN 953 Safety of machinery - Guards - DIN EN ISO 12100...
  • Page 5: Delivery / Handling

    If there is any damage or even a suspicion of damage, the recipient must indicate this on the consignment note and have it countersigned by the haulier. The recipient of the goods must notify WOLF of the relevant facts without delay. Handling The units must only be transported in their installation position.
  • Page 6: Installation Information

    Installation information Foundation A level, horizontal and load-bearing surface is required to site and install the Please note units and unit components. Base frames must be levelled horizontally; foundation plinths must also be KG 40-100: level and horizontal. The entire lower unit frame must sit on the foundation; point loads are not permissible.
  • Page 7 Installation information KG 15-100 Sealing tape KG 40-100 Only with recirculation air damper with self-tapping hexagon screws Ø 8x25 Sealing tape Unit arrangement: Stacked units are delivered separately and must be linked together on site stacked or adjacent using the unit connectors and drilling screws provided. Upper and lower or adjacent unit sections cannot be fitted together until the various transport units have been assembled at the final installation site.
  • Page 8 Installation information Version for disassembly The units are delivered fully assembled. To facilitate handling, they can be (on request) taken apart and reassembled in the installation room. KG 40-100 With the version for disassembly, the frame sections split in the centre and are secured with a flat steel bar or angle bracket (secured with screws).
  • Page 9 Installation information On-site cooler installation: Remove casing and mist eliminator with condensate pan (mist eliminator is placed in the guide rails for shipping). Apply sealant to the mist eliminator frame and secure to the cooler bank. Please note The condensate drain apertures in the mist eliminator must be facing downwards. Direction of air flow Depending on the direction of the air flow, the removable cover panel must be fitted at the air intake on the collector side of the cooler bank.
  • Page 10 Installation information Ball siphon In order to drain away the condensate reliably, join a ball siphon to the condensate drain connector onto the drain pan for the cooler/direct evaporator and onto the KGX/KGXD plate heat exchanger pan. Please note that a siphon must be fitted to every condensate drain connector. It is not permissible to join several drains to a common siphon.
  • Page 11: Electrical Connection

    Installation information / Electrical connection Intake/discharge hood Fit the side sections and top section as shown in the diagram using the screws provided. Screws Upper section Side sections (drip moulding on outside) In the version with two intake/discharge hoods, one above the other, the upper hood protrudes over the lower one.
  • Page 12 Electrical connection Electrical connection Electrical connection should only be carried out by an electrician in accordance with the applicable regulations (VDE, power supply utility, etc.). If the supply or extract air fan is shut down or fails, all control valves must close automatically and the hot/cold water and scrubber pumps must stop. Only use normally closed control valves and a frost stat without restart lock.
  • Page 13 Electrical connection Single speed control Motors up to 2.2 kW are usually started directly; from 3 kW they are started in star delta configuration. Configuration of phase windings The ends of the 3 phase windings go to the Y/∆ switch Configuration on terminal board Y/∆...
  • Page 14: Commissioning

    Commissioning In accordance with DIN EN 1886, the unit must be opened with tools. Wait for the fan to come to a complete standstill before opening the inspection doors. When the doors are opened, negative pressure may draw in loose objects, which could destroy the fan or even cause a risk to life if items of clothing are drawn in.
  • Page 15 Commissioning Louvre damper The louvre dampers may need to be insulated on site against both sound (accessory) emission and the formation of condensate. In the case of louvre dampers, follow the separately supplied installation instructions for the damper servomotor. Louvre damper drive shaft: 15 x 15 mm If louvre dampers are located on the pressure side, open them fully before commissioning the fan.
  • Page 16 Commissioning Electric heater To prevent overheating, note the following minimum air volumes (in m³/h): Unit type KG Minimum air 550* 900 1600 1600 2500 acc. to unit volume (m design horizontal + vertical ↑ Minimum air 800* 1300 1300 2200 2200 3200 acc.
  • Page 17: Commissioning

    Commissioning Cooler Before filling the refrigerant circuit with refrigerant, take suitable steps to ensure (direct evaporator) that no residual moisture remains in the pipework system (e.g. evacuate or purge with dry nitrogen). Check the discharge temperature and evaporation temperature: minimum temperature +2 °C.
  • Page 18: Maintenance

    Maintenance Before starting any maintenance work, turn the system ON/OFF switch OFF and secure against reconnection. If it is switched ON again unintentionally, people who enter the unit are at risk from rotating parts. Wait for the fan to come to a complete standstill before opening the inspection doors.
  • Page 19 Maintenance Flat belt drive Check that the fan drive shaft is exactly parallel to the motor drive shaft. Please note Check that the pulleys are in perfect alignment. Thoroughly clean all pulley running surfaces of dirt, oil and grease. Check marks Before the test run, turn the pulleys by hand to check the belt is running correctly.
  • Page 20: Frost Protection

    Maintenance / Frost protection Scrubber Clean scrubbers and mist eliminators at regular intervals. The cleaning cycles depend on the operating mode, air condition and water quality. For maintenance, drain the pan and rinse with clean water or a high pressure cleaner.
  • Page 21: Checklist

    Checklist Recommended checklist for hygienic operation and maintenance of air handling systems Activity Action if required Months Outdoor and exhaust air apertures Structural units/appliance casing Check for contamination, damage and Clean and repair corrosion Air filter Check for impermissible contamination and Replace affected air filters if last filter stage damage (leaks) replacement was within last 6 months,...
  • Page 22: Notes

    Notes 3040530_201503...