Wolf AHU TE Installation And Maintenance Instructions Manual page 30

Air-handling unit
Table of Contents

Advertisement

Heat exchanger
(heating coil / cooling coil / KGX)
Dampers
Scrubber
Filter
Quick- action
Bag filter
clamp
Operator side
Activated charcoal filter
30
Maintenance
Check periodically for contamination and clean as necessary.
Clean the heat exchanger by:
- Vacuum extraction
- Blowing down with compressed air
- Spraying with water or steam
Ensure that the air/water/steam pressure for cleaning is not in excess of 5 bar, otherwise
Note
there is a risk of mechanical damage to components.
Check the condensate drain.
Open the siphon, clean it and refill it.
Use a commercially available descaling agent to clean the drop-eliminator sections.
Never oil dampers. Oil could damage the plastic used. In that case the damper function
would no longer be ensured.
Blow the dampers clean with compressed air; no other maintenance is required.
Regularly clean the scrubber and the mist eliminator. Cleaning intervals are subject to
operating method, air condition and water quality.
Maintenance involves draining the tray and rinsing it with clean water or a high pressure
cleaner.
Spray pipework and nozzle assembly only with reduced water pressure.
Parts could be damaged by a jet of water at excessive pressure.
Commercially available descaling agents can be used.
Note
Never use foaming cleansers.
The scrubber pump is maintenance free.
However, when cleaning the scrubber it is advisable to flush the pump and the pipework
with clean water.
If the scrubber is out of use for a longer period of time, start the pump weekly and allow it
Note
to run for approx. 5 minutes to prevent the bearings from seizing (never run the pump dry).
Wear protective clothes, protective gloves and a respirator when exchanging the
filter!
Contaminated filters are dangerous to human health. Contact with filter dust can
cause allergic reactions of the skin, eyes and respiratory organs
If filter inserts require cleaning or replacement, open the inspection door
and pull them to the side and out of the casing.
Category G4 synthetic fibre filter mats used as filter inserts can be regenerated. The
mats can be tapped clean, blown clean, vacuum cleaned or washed out in a solution
of commercially available fine detergent and lukewarm water. Never wring out the
mats.
Bag filters cannot be regenerated. Replace the bag filters when the pressure drop
exceeds the permissible maximum because of clogging.
When bag filter inserts require replacement, open the inspection door and release the
quick action clamp, then pull the bag to the side and out of the casing.
(pull quick action clamp with a tool = remove filter;
(push quick action clamp with a tool = filter tensioned)
Note:
Pull the swallow tail seals off the spent filters and push them into position on
the replacement filters. This is important to ensure that the new filters are reinstalled
correctly.
Replace the activated charcoal filters (cartridges) if they are saturated (expiry of the
specified operating time).
The cartridges are fastened with special bolts (bayonet connection). Rotate the cart-
ridges and pull them towards you out of the frame. When exchanging the activated
charcoal filter cartridges, the pre-filters should also be renewed in order to achieve
optimum service lives of the activated charcoal filters.