With the RDF110 and RDF110.2, a number of control parameters can be readjusted to
optimize the control performance. These parameters can also be set during operation
without opening the unit. In the event of a power failure, all control parameter settings
will be maintained.
The parameters can be changed as follows:
1.
Set the controller to Protection (Standby)
2.
Press buttons
within 2 seconds, press button
show "P01".
3.
Select the required parameter by repeatedly pressing buttons
+
-
+
-
P01
P02
4.
By pressing buttons
parameter appears, which can be changed by repeatedly pressing buttons
or
.
5.
By pressing buttons
press of a button, the last parameter will be displayed again.
6.
If you wish to display and change additional parameters, repeat steps 3
through 5.
7.
10 seconds after the last display or setting, all changes will be stored and the
controller returns to Protection (Standby).
Parameters not used by the RDF110.2 are not available and cannot be displayed.
The factory setting of the control parameters can be reloaded as follows:
1.
Set the controller to Protection (Standby)
2.
Press buttons
within 2 seconds, press operating mode selector button
Then, the display will show "888" during the reloading process.
Room Temperature Controllers
and
simultaneously for 3 seconds. Release them and,
again for 3 seconds. Then, the display will
+
+
-
P22
P25
3057z03
and
simultaneously, the current value of the selected
and
simultaneously again or 5 seconds after the last
and
simultaneously for 3 seconds. Release them and,
.
and
-
+
-
-
P98
P99
.
2 times.
:
N3057en