11. HOW TO EXCHANGE COMPRESSOR
11-1. Exchanging Procedure of Compressor (Outline)
START
Has refrigerant recovery work been done?
Turn off the leakage breaker.
Remove the defective compressor.
Mount a service compressor.
Leakage check
Vacuuming
Charge the refrigerant.
END
11-2. Exchange of Compressor
For exchange of compressors, refer to (11) Compressor in Section of 13. Detachments.
NO
YES
Never recover the refrigerant to the outdoor unit.
– 74 –
Open PMV forcedly and then recover refrigerant
using a refrigerant recovery unit.
For the refrigerant recovery work during reinstallation
of repair work, be sure to use the refrigerant recovery unit.
Recovery of refrigerant to the outdoor unit is unavailable;
otherwise a serious accident such as explosion or
injury may be caused.
FILE NO. SVM-18042