Toshiba RAV-GM301ATP-E Service Manual page 22

Hide thumbs Also See for RAV-GM301ATP-E:
Table of Contents

Advertisement

RAV-GM401AT P
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Outer dia. : 12.7mm
Thickness : 0.8mm
4-way valve
(STF-0108-Z)
Accumulater tank
NOTE :
• The maximum pipe length of this air conditioner is 20m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Muffler
Muffler
TD
Compressor
TS
TO
Outdoor heat
Split capillary
exchanger
2-dia. 1.2 × 80
Distributor
TE
Propeller fan
OUTDOOR UNIT
– 22 –
T1 Temp. measurement
TC
TA
Max.
Min.
Chargeless : 15m
Charge
(16 to 20m)
Strainer
Pulse Modulating valve
at liquid side
(CAM-BD16TCTH-2)
Refrigerant amount: 1.40kg
NOTE:
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
FILE NO. SVM-18042
:
20m
: 2m
: 20g/m