T7300E SERIES 2000 COMMERCIAL MICROELECTRONIC HEAT PUMP THERMOSTAT
To start the system test:
CAUTION
The minimum off time for compressors is bypassed
during the Installer System Test. Equipment
damage can occur if the compressor is cycled too
quickly.
Press and hold the increase
the same time, until 10 appears. All segments of the LCD
are displayed for three seconds before 10 appears. See
Fig. 5 and 6.
Set Program
Set Program
Start Time
Set Day/Time
Set Day/Time
Em Ht
Em Ht
Aux Ht
Comm
Mon
TueWedThuFriSatSun
Un
Occupied 12 Override
System
Em Heat
Off
Cool
Auto
Fig. 5. Display of all the segments of the LCD.
Key to
Press
Heating Equipment System Test
Heat/Cool Settings
Emergency Heating Equipment System Test
Heat/Cool Settings
Cooling Equipment System Test
Heat/Cool Settings
Fan Equipment System Test
Heat/Cool Settings
62-0124—3
and
decrease keys, at
Temporary Setting Enrg
AM
PM
%Humid
Heat
Cool
Remote
In
Recovery
Auto
Only
Lo
Med
Hi
Fan
Wait
On
Table 4. Installer System Test Options.
Test
Number
10
Enter heating equipment system test.
11
Stage-one heat comes on. The system fan is also energized.
12
Stage-two heat comes on. Stage-one heat and system fan remain on.
13
Stage-three heat comes on. Stage-one and stage-two heat with the system fan
are on.
12
Stage-three heat turns off.
11
Stage-two heat turns off.
10
Stage-one heat and system fan turn off.
20
Change from heating to emergency heating equipment system test.
21
Emergency heat and system fan come on.
20
Emergency heat turns off.
30
Change from heating or emergency heating to cooling equipment system test.
31
Stage-one cooling and system fan come on.
32
Stage-two cool comes on. Stage-one cool and system fan remain on.
31
Stage-two cool turns off.
30
Stage-one cool and system fan turn off.
40
Change from cooling to fan equipment system test.
41
Fan comes on.
40
Fan turns off.
Refer to Table 4 and Thermostat Information section for
directions and results of the specific system tests.
Sav
NOTE: Press Run Program to exit the system test. The
Room
system test times out after four minutes without
any key presses.
Duct
Auto
M4916
Description
6
TEST NUMBER
Fig. 6. Display of test number.
M10257A
(continued)