List Of Installer Parameters - Potterton SIRIUS THREE FS 50 Installation Manual

Floor-standing condensing gas boiler
Table of Contents

Advertisement

Tab.54
Menu Operator section
Parameter
Parameter
number
24
Lighting
29
Units
40
Used as
42
Assignment device
1
43
Action operation
54
Readjustment room
sensor
70
Software version
Tab.55
Temps / mode CH1 - Temps / mode CH2 menus - Temps / mode CH3
Parameter number
Heating
Heating
Heating
circuit 1
circuit 2
circuit 3
714
1014
1314
720
1020
1320
730
1030
1330
732
1032
1332
740
1040
1340
741
1041
1341
7609493 - v08 - 24072018
9.1.4
Description
Off
Temporarily
Permanently
°C, bar
°F, PSI
Operator unit 1 : The control system unit is installed on the boiler.
Room unit 1 : The control system unit is configured as a room tem­
perature unit for heating circuit 1.
Room unit 2 : The control system unit is configured as a room tem­
perature unit for heating circuit 2.
Room unit 3 : The control system unit is configured as a room tem­
perature unit for heating circuit 3.
As Room Temperature Unit 1, the action of the control system unit can
be assigned to CH1 or to two heating circuits:
Temps / mode CH1
Central heating 1 and 2
Central Heating 1 and 3
All central heatings
Locally : The room temperature unit controls only the respective
heating circuit.
Centrally : Only room temperature unit 1 can be centralised. It also
controls the domestic hot water and standby mode.
-3°C to +3°C
Parameter
Description
Frost protection
setpoint
Heating curve
Heating curve gradient: The regulator calcu­
slope
lates the flow temperature set point which is
used for the control system, according to out­
side weather conditions.
Summer/winter
Limit temperature for switching between Heat­
heating limit
ing/Protection mode. Triggers or shuts down
the heating in the course of the year according
to variations in outside temperature. This
switch is made automatically in Automatic
Mode.
24-hour heating
The heating is shut down when the outside
limit
temperature is equal to the room temperature +
parameter 732 (deactivated in Comfort mode).
Flow temp setpoint
The flow set point calculated is limited by the
min
set value.
Flow temp setpoint
The flow set point calculated is limited by the
max
set value.

List of installer parameters

9 Settings
Factory set­
ting
Temporarily
°C, bar
Operator unit
1
All central
heatings
Centrally
0°C
Unit
Factory set­
ting
°C
6
Heating
circuit 1:
1.5
Heating
circuit 2:
1.5
Heating
circuit 3:
1.5
20
°C
0
°C
25
°C
80
73