Samsung AVMKH020EA4 Service Manual page 233

System air conditioner
Hide thumbs Also See for AVMKH020EA4:
Table of Contents

Advertisement

Troubleshooting
11-5-9 Breakaway of PWM valve connecter(Not controlled the capacity of compressor)/shortage of refrigerant
• The T-discharge rises.
• The temperature of indoor unit inlet/outlet is down to
the below 0˚C.
• P3 or P0 error is occurred at the outdoor unit PCB.
11-47
Phenomenon
Check method
• Check if the PWM connecter is departed.
• After checking the pressure of refrigerant, recharge the
refrigerant.
Samsung Electronics