WIRING
PRECAUTIONS
• Make sure to properly wire to the terminal block (European type) in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions described
in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
3.1 Applicable cable and terminal tightening torque
3.1.1
Terminal block (European type)
1) Wire size
- The power supply wire should use 22-20 AWG wire.
2) Applicable cable
Type
Wire size
Single-wire
0.3 mm
2
to 0.5 mm
2
(AWG22 to 20)
2-wire
2
2 pieces of 0.3 mm
(AWG22)
3) Termination of cable end
Strip the coating of strand wire and twist the cable core before connecting it, or
strip the coating of single wire before connecting it.
An alternative connection is to use a ferrule with insulating sleeve.
<Reference>
Manufacturer
Model
Caulking tool
CRIMPFOX 6
Phoenix Contact Co., Ltd.
AI 0.5-8WH
(or CRIMPFOX 6T-F
*1 Old model name: CRIMPFOX ZA 3
*2 Old model name: CRIMPFOX UD 6
- Strand wire/single wire
- Ferrule with insulation sleeve
Insulation sleeve
Contact area
(Crimp area)
9 mm
(0.35")
2.6 mm (0.1")
14 mm (0.55")
When using a ferrule with insulation sleeve, choose a wire with proper cable
sheath referring to the above outside dimensions, or otherwise, the wire cannot
be inserted easily.
The tightening torque must be 0.22 to 0.25 N
m. Do not tighten terminal screws
with a torque outside the above-mentioned range. Failure to do so may cause
equipment failures or malfunctions.
3.2 Power Supply Wiring
For the power supply wiring, refer to the following manual.
→ FX
/FX
/FX
/FX
/FX
Series User's Manual - Analog Control Edition
3S
3G
3GC
3U
3UC
3.3 Selection of resistance thermometer sensors
→ For the terminal layout, refer to Section 1.2
Precautions on resistance thermometer wiring
• When using a 2-wire temperature sensor type, short-circuit the [L-] terminal
and the [I-] terminal. For the lead wire use a 10 Ω resistance or less per line.
• Separate the cable of the resistance thermometer sensors from the other
power cables or areas easily affected by inductive noise (of the commercial
power, etc.).
Example of resistance thermometer wiring
Resistance thermometer
wiring
3-wire
47 k
sensors
Terminal
Shield wire
type
block
L+
L-
I-
2-wire
sensors
47 k
type
L+
L-
*2
I-
External power supply
wiring
24+
24 V DC
*1
24-
Class-D grounding
L+, L-, I-, ch:  represents the channel number.
*1 24 V DC service power supply of the FX
/FX
3S
3G
used.
*1
*2 When using a 2-wire temperature sensor type, short-circuit the [L-] terminal
*2
and the [I-] terminal.
)
3.4 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" of the
following figure.
For details, refer to the respective PLC User's manual Hardware Edition.
8 mm
Other
Other
PLC
PLC
(0.31")
equipment
equipment
Independent grounding
Shared grounding
(Best condition)
(Good condition)
• The grounding wire size should be AWG 22-20 (0.3-0.5 mm
• The grounding point should be close to the PLC, and all grounding wire should be
as short as possible.
4. Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric representative.
• Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
• Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION AND
STORAGE PRECAUTIONS
• The product is a precision instrument. During transportation, avoid impacts
larger than those specified in the general specifications by using dedicated
packaging boxes and shock-absorbing palettes. Failure to do so may cause
failures in the product. After transportation, verify operation of the product and
check for damage of the mounting part, etc.
4.1 Applicable PLC
PNK-ADP
Model name
FX
Series PLC
Ver. 1.00 or later (from first production)
+5 V
3S
FX
Series PLC
Ver. 1.00 or later (from first production)
3G
47 k
FX
Series PLC
Ver. 1.40 or later (from first production)
3GC
ch
1 M
FX
Series PLC
Ver. 2.20 or later (from first production)
3U
Ver. 1.30 or later (from the production manufactured in
1 M
FX
Series PLC
3UC
August, 2004 with SER No. 48****)
The version number can be checked by monitoring D8001/D8101 as the last three
+5 V
digits indicate it.
4.2 General Specifications
47 k
Items other than the following are equivalent to the those of the PLC main unit.
1 M
ch
For general specifications, refer to the respective PLC User's manual Hardware Edition.
Item
1 M
Dielectric withstand
500 V AC for one minute
voltage
+5 V
5 MΩ or higher by 500 V DC
Insulation resistance
insulation resistance tester
4.3 Power Supply Specifications
Item
A/D conversion
24 V DC +20 %/-15 %, 50 mA for 24 V DC
circuit driving power
Connect a 24 V DC power supply to the terminal block.
5 V DC, 15 mA
Interface driving
5 V DC power is supplied from the internal power supply of
power
/FX
Series PLC can also be
3U
main unit.
4.4 Performance Specifications
Item
Centigrade (°C)
Platinum resistance thermometer sensor (2-wire or 3-wire) Pt1000
Input signal
Nickel resistance thermometer sensor (2-wire or 3-wire) Ni1000
Rated
Pt1000
-50 °C to +250 °C
temperature
Ni1000
Other
range
PLC
equipment
Pt1000
Digital output
Ni1000
Common grounding
Pt1000
(Not allowed)
Resolution
Ni1000
2
).
±0.5 % for full scale (when ambient temperature is 25 °C±5 °C)
Total
±1.0 % for full scale (when ambient temperature is in the range of 0
accuracy
to 55 °C)
• FX
/FX
3U
3UC
A/D
(The data will be updated at every scan time of the PLC.)
conversion
• FX
/FX
3S
3G
time
(The data will be updated at every scan time of the PLC.)
- Pt1000
+2560
+2500
-50°C
0
Input charac-
teristics
- Ni1000
+1150
+1100
-40°C
0
Applicability
Item
Insulation
method
Occupied
points
「电器电子产品有害物质限制使用标识要求」的表示方式
Specification
Note: This symbol mark is for China only.
含有有害6物质的名称, 含有量, 含有部品
Between all terminals and
 本产品中所含有的有害 6 物质的名称, 含有量, 含有部品如下表所
ground terminal of PLC main
示。
unit
Specification
部件名称
可编程
控制器
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
Description
规定的限量要求以下。
Fahrenheit (°F)
×: 表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
26572规定的限量要求。
JIS C 1604-1997
DIN 43760-1987
基于中国标准法的参考规格: GB/T15969.2
Pt1000
-58 °F to +482 °F
-40 °C to +110 °C
-40 °F to +230 °F
Ni1000
-500 to +2500
Pt1000
-580 to +4820
-400 to +1100
Ni1000
-400 to +2300
Pt1000
0.2 ° F
0.1 °C
Ni1000
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
Series PLC : 200 μs
occur as a result of using the contents noted in this manual.
/FX
Series PLC : 250 μs
3GC
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
- Pt1000
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
+4928
+4820
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
-58°F
0
and other tasks.
+482°F
+250°C
-580
-500
-550
-670
- Ni1000
This product has been manufactured as a general-purpose part for general
+2390
+2300
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
-40°F
0
Mitsubishi Electric.
+110°C
+230°F
This product has been manufactured under strict quality control. However
-400
-400
when installing the product where major accidents or losses could occur if the
-450
-490
product fails, install appropriate backup or failsafe functions in the system.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Description
Centigrade (°C)
Fahrenheit (°F)
• The photocoupler is adopted to insulate the analog input area
from the PLC.
• The DC/DC converter is adopted to insulate the power supply
line from the analog input area.
• Channels are not insulated from each other.
0 point (This number is not related to the maximum number of
input/output points of the PLC.)