Hoshizaki KM-1301SAH/3 Service Manual

Hoshizaki KM-1301SAH/3 Service Manual

Stackable crescent cuber
Hide thumbs Also See for KM-1301SAH/3:
Table of Contents

Advertisement

Hoshizaki
Hoshizaki America, Inc.
"A Superior Degree
of Reliability"
www.hoshizaki.com
Stackable Crescent Cuber
Models
KM-1301SAH/3, SWH/3, SRH/3
KM-1400SWH-M, SWH3-M
KM-1601SAH/3, SWH/3, SRH/3
KM-1900SAH/3, SWH/3, SRH/3
KM-2100SWH3, SRH3
KM-2500SWH3, SRH3
KMH-2000SWH/3, SRH/3
SERVICE MANUAL
Number: 73208
Issued: 7-7-2015
Revised: 8-11-2015

Advertisement

Table of Contents
loading

Summary of Contents for Hoshizaki KM-1301SAH/3

  • Page 1 Hoshizaki Hoshizaki America, Inc. Stackable Crescent Cuber Models KM-1301SAH/3, SWH/3, SRH/3 KM-1400SWH-M, SWH3-M KM-1601SAH/3, SWH/3, SRH/3 KM-1900SAH/3, SWH/3, SRH/3 KM-2100SWH3, SRH3 KM-2500SWH3, SRH3 KMH-2000SWH/3, SRH/3 SERVICE MANUAL “A Superior Degree of Reliability” www.hoshizaki.com Number: 73208 Issued: 7-7-2015 Revised: 8-11-2015...
  • Page 2 Hoshizaki provides this manual primarily to assist qualified service technicians in the service of the appliance. Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance. Phone: 1-800-233-1940; (770) 487-2331 Fax: 1-800-843-1056;...
  • Page 3: Table Of Contents

    IMPORTANT This manual should be read carefully before the appliance is serviced. Read the warnings and guidelines contained in this manual carefully as they provide essential information for the continued safe use, service, and maintenance of the appliance. Retain this manual for any further reference that may be necessary. CONTENTS Important Safety Information ....................
  • Page 4 III. Controls and Adjustments ....................46 A. Control Board Layout ....................47 1. "E" Control Board ....................47 2. "G" Control Board ....................48 B. LED Lights and Audible Alarm Safeties ............... 49 1. "E" Control Board ....................49 2. "G" Control Board ....................50 C.
  • Page 5 16. KM-1601SRH3 with URC-21F Auxiliary Codes: R-0, R-1, and some S-1 .... 81 17. KM-1601SRH3 with URC-21F Auxiliary Codes: some S-1 and S-2 and Later ..82 18. KM-1601SRH3 with URC-22F Auxiliary Codes: S-2 and Later ......83 19. KM-1900SAH ....................... 84 20.
  • Page 6: Important Safety Information

    Important Safety Information Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property. WARNING Indicates a hazardous situation which could result in death or serious injury.
  • Page 7 WARNING, continued • The appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. •...
  • Page 8: Construction And Water/Refrigeration Circuit Diagram

    I. Construction and Water/Refrigeration Circuit Diagram A. KM Construction 1. Air-Cooled Models (SAH/3) Spray Tubes Low-Side Service Valve Inlet Water Valve High-Side Service Valve Evaporator Assembly Thermostatic Expansion Valves Water Supply Inlet Junction Box Hot Gas Valve Check Valves (refrigeration) Cleaning Valve Condenser Control Box...
  • Page 9: Water-Cooled Models (Swh/3/-M)

    2. Water-Cooled Models (SWH/3/-M) Spray Tubes Low-Side Service Valve Inlet Water Valve High-Side Service Valve Evaporator Assembly Thermostatic Expansion Valves Water Supply Inlet Junction Box Hot Gas Valve Check Valves (refrigeration) Water-Cooled Condenser Cleaning Valve Check Valve (water) Water Pump Water Regulating Float Switch Valve...
  • Page 10: Remote Models (Srh/3)

    3. Remote Models (SRH/3) Low-Side Service Valve Spray Tubes Inlet Water Valve High-Side Service Valve High-Side Liquid Service Valve Evaporator Assembly Water Supply Inlet Hot Gas Valve Junction Boxes Check Valves Cleaning Valve (refrigeration) Thermostatic Expansion Valves Check Valve Receiver (water) Water Pump Control Box...
  • Page 11: Kmh Construction

    B. KMH Construction 1. Water-Cooled Models (SWH/3) Inlet Water Valve Spray Tubes High-Side Service Valve Thermostatic Expansion Valves Check Valves Evaporator Assembly (refrigeration) Cleaning Valve Transformer Box (3 phase model) Check Valve (water) Water Pump Control Box Float Switch Control Switch Low-Side Service Valve Bin Control Thermostat Model Shown: KMH-2000SWH3...
  • Page 12: Remote Models (Srh/3)

    2. Remote Models (SRH/3) Inlet Water Valve Spray Tubes Thermostatic Expansion Valves Check Valves Evaporator Assembly (refrigeration) High-Side Service Valve Cleaning Valve Check Valve Transformer Box (water) (3 phase model) Water Pump Float Switch Control Box Low-Side Service Valve Control Switch Bin Control Thermostat Model Shown: KMH-2000SRH3 High-Pressure Switch...
  • Page 13: Bin Control

    Bin Control Bulb Holder C Silicone Hose Bin Control Extension Bracket Bin Control Bulb Holder Z Bracket Used for Hoshizaki B-1300, B-1500, B-1650, and Non-Hoshizaki Ice Stoarage 1b. Stacked Thermostatic Bin Control Upper Bin Control Bulb Holder Lower Bin Control Bulb Holder...
  • Page 14: 2A. Single Mechanical Bin Control

    2a. Single Mechanical Bin Control Mechanical Bin Control Connection Overview Wire Harness Bin Control Cable Connector to Connector B Wire Harness Connector A (for upper unit) Wire Harness Connection Detail Control Board Red K4 Connector Wire Harness Connector B (for upper unit) Wire Harness Bin Control Connector A...
  • Page 15: Water/Refrigeration Circuit Diagram

    D. Water/Refrigeration Circuit Diagram 1. Air-Cooled Models (SAH/3)
  • Page 16: Water-Cooled Models (Swh/3/-M)

    2. Water-Cooled Models (SWH/3/-M)
  • Page 17: 3A. Remote Models (Srh/3) Except Km-2500Srh3

    3a. Remote Models (SRH/3) Except KM-2500SRH3 Condenser Unit with Headmaster (CPR)
  • Page 18: 3B. Remote Models (Srh3) Km-2500Srh3

    3b. Remote Models (SRH3) KM-2500SRH3 Condenser Unit without Headmaster (CPR)
  • Page 19: Sequence Of Operation And Service Diagnosis

    II. Sequence of Operation and Service Diagnosis A. Sequence of Operation Flow Chart 1. "E" and "G" Control Board without Harvest Pump Timer Operation...
  • Page 20: G" Control Board With Harvest Pump Timer Operation

    2. "G" Control Board with Harvest Pump Timer Operation...
  • Page 21: 3A. Thermostatic Bin Control Shutdown

    3a. Thermostatic Bin Control Shutdown...
  • Page 22: 3B. Mechanical Bin Control Shutdown

    3b. Mechanical Bin Control Shutdown...
  • Page 23: Service Diagnosis

    B. Service Diagnosis WARNING • The appliance should be diagnosed and repaired only by qualified service personnel to reduce the risk of death, electric shock, serious injury, or fire. • Risk of electric shock. Control switch in "OFF" position does not de-energize all loads Use extreme caution and exercise safe electrical practices.
  • Page 24: E" And "G" Control Board Without Harvest Pump Timer Diagnosis

    1. "E" and "G" Control Board without Harvest Pump Timer Diagnosis 3) Power On: Turn on the power supply, then move the control switch to the "ICE" position. A 5-sec. delay occurs. • "E" Control Board: CB red "POWER OK" LED turns on. •...
  • Page 25 5) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV continues. Comp, FMR, and HGV energize. CB monitors the warming of the evaporator via the thermistor located on the suction line. When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 &...
  • Page 26 b) Comp and FMR Diagnosis: If Comp and FMR de-energize once freeze begins, check that appliance has not shut off on HPS ("POWER OK" LED off). If so, check "3)b) HPS Diagnosis" above. If "POWER OK" LED is on, check for 115VAC at CB K1 #1 (V) or #9 (V) to neutral (W).
  • Page 27 h) Freeze Termination Diagnosis: After 5 min. in freeze, disconnect CB K5 FS connector. 15 sec. later appliance should switch out of the freeze cycle (15 second delay after FS opens before terminating the freeze cycle). If appliance remains in freeze longer than 15 sec.
  • Page 28 8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5 above. Note: Appliance continues to cycle until BC is satisfied or power is turned off. The appliance always restarts at the 1-min. fill cycle. 9) Shutdown: "E" and "G" Control Board When the appliance is running, hold ice in contact with the thermostatic bulb.
  • Page 29: G" Control Board With Harvest Pump Timer Diagnosis

    2. "G" Control Board with Harvest Pump Timer Diagnosis 3) Power On: Turn on the power supply, then move the control switch to the "ICE" position. A 5-sec. delay occurs. CB red "POWER OK" LED and green "BC CLOSED" LED turn on.
  • Page 30 5a) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV and X11 relay continue. Comp, FMR, HGV, and X10 relay energize. CB monitors the warming of the evaporator via the thermistor located on the suction line. When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ...
  • Page 31 If 115VAC is present on terminal #3 (P) and not on terminal #5 (Y), replace X10 relay. If 115VAC is present on X10 relay terminal #7 (Y) and PM is not energized, check for 115VAC at X10 relay terminal #4 (R) to neutral (W) and terminal #6 (DBU) to neutral (W).
  • Page 32 c) WV and HGV Diagnosis: If WV is energized, check for 115VAC at CB K1 #6 (O) to neutral (W). If 115VAC is present after PM energizes in harvest cycle, replace CB. If 115VAC is not present, replace WV (bypassing). If HGV did not de-energize at the end of harvest, check for 115VAC at CB K1 #2 (P) to neutral (W).
  • Page 33 7) Pump-Out Cycle – LEDs 1, 3, and 2 are on (10/20 second pump-out). Timing of the first pump-out is determined by S4 dip switch 5 & 6. See the table below. "G" Control Board Settings S4 Dip Switch Setting Pump-Out 1st Pump-Out Frequency "G"...
  • Page 34 8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5a) above. Note: Appliance continues to cycle until MBC is satisfied or power is switched off. The appliance always restarts at the 1-min. fill cycle. 9) Shutdown: "G" Control Board a) Thermostatic Bin Control (TBC): When the appliance is running, hold ice in contact with the thermostatic bulb.
  • Page 35: Control Board Check

    C. Control Board Check Before replacing CB that does not show a visible defect and that you suspect is bad, always conduct the following check procedure. This procedure will help you verify your diagnosis. Alarm Reset: If CB is in alarm (beeping), press the "ALARM RESET" button on CB while CB is beeping.
  • Page 36: Bin Control Check

    D. Bin Control Check 1. Thermostatic Bin Control Check BC shuts down the icemaker within 10 sec. when ice contacts the thermostatic bulb, regardless of the cycle at activation. NOTICE When the ambient temperature is below 45°F (7°C), BC opens and shuts down the appliance even if the ice storage bin is empty.
  • Page 37: Mechanical Bin Control Check

    2. Mechanical Bin Control Check a) Mechanical Bin Control Check This appliance uses a lever-actuated proximity switch to control the ice level in the storage bin. No adjustment is required. To check MBC, follow the steps below. 1) Turn off the power supply. 2) Remove the front panel, then move the control switch to the "OFF"...
  • Page 38 5) Remove the actuator paddle from the switch mount. See Fig. 2. 6) Wipe down MBC with a mixture of 1 part of Hoshizaki "Scale Away" and 25 parts of warm water. Rinse the parts thoroughly with clean water.
  • Page 39: Float Switch Check And Cleaning

    E. Float Switch Check and Cleaning FS is used to determine that there is sufficient water in the water tank after the 1-min. fill cycle and after each harvest cycle. FS is also used to determine that the appropriate volume of water has been converted into ice before switching out of the freeze cycle. No adjustment is required.
  • Page 40: Float Switch Cleaning

    Be careful not to bend the retainer rod excessively when removing it. 7) Wipe down FS housing, shaft, float, and retainer rod with a mixture of 1 part Hoshizaki "Scale Away" and 25 parts warm water. Clean the inside of the rubber boot and hose with cleaning solution.
  • Page 41: Thermistor Check

    F. Thermistor Check To check thermistor resistance, follow the steps below. 1) Turn off the power supply. 2) Remove the front panel. Move the control switch to the "OFF" position. 3) Remove the control box cover. 4) Remove the thermistor from the refrigerant tubing. 5) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3 min.
  • Page 42: Diagnostic Tables

    G. Diagnostic Tables 1. No Ice Production No Ice Production - Possible Cause 1. Power Supply a) Off, blown fuse, or tripped breaker. b) Not within specifications. 2. Main Transformer a) Voltage tap switch not set to proper voltage. (KM-1301S_H auxiliary code D-1 b) Coil winding open or shorted.
  • Page 43 Water leaks causing short freeze time. 2. Freeze-Up Defrost and clean the icemaker prior to diagnosing freeze-up. Fill out a freeze-up checklist. See the Hoshizaki America Technician's Pocket Guide or contact your local distributor for a copy of the freeze-up checklist. Freeze-Up - Possible Cause Harvest Cycle 1.
  • Page 44 Freeze-Up - Possible Cause 10. Thermistor a) Loose, disconnected, or defective. See "II.F. Thermistor Check" 11. Thermostatic Expansion Valve a) Defective. 12. Hot Gas Valve a) Closed or restricted. 13. Liquid Line Valve a) Open. Freeze Cycle 1. Evaporator a) Scaled up. b) Damaged.
  • Page 45 Low Ice Production - Possible Cause 9. Compressor a) Inefficient or off. 10. Liquid Line Valve a) Erratic or open. 11. Thermostatic Expansion Valve a) Defective. Long Freeze Cycle 1. Evaporator a) Scaled up, dirty. 2. Float Switch a) Scaled up, dirty. See "II.E.
  • Page 46: Controls And Adjustments

    III. Controls and Adjustments • A Hoshizaki exclusive control board is employed in KM and KMH series appliances. • All models are pretested and factory adjusted. • For a control board check procedure, see "II.C. Control Board Check." NOTICE • Fragile, handle very carefully.
  • Page 47: Control Board Layout

    A. Control Board Layout 1. "E" Control Board "E" Control Board • "OUTPUT TEST" Button • "ALARM RESET" Button • S4 Dip Switch (used to test relays on control board) • Freeze Timer • K3 (white) Connector LED (yellow) Thermistor (harvest control and high temperature safety) •...
  • Page 48: G" Control Board

    2. "G" Control Board "G" Control Board • Bin Control Switch Closed LED (green) • "OUTPUT TEST" Button • S4 Dip Switch • "ALARM RESET" Button (on continuously (used to test relays on control board) in thermostatic bin control application) •...
  • Page 49: Led Lights And Audible Alarm Safeties

    B. LED Lights and Audible Alarm Safeties 1. "E" Control Board At startup, a 5-second delay occurs while the control board conducts an internal timer check. A beep occurs when power is turned off. The red "POWER OK" LED indicates proper control voltage and remains on unless a control voltage problem occurs.
  • Page 50: G" Control Board

    2. "G" Control Board At startup, a 5-second delay occurs while the control board conducts an internal timer check. A beep occurs when the control switch is moved to the "ICE" position. The red "POWER OK" LED indicates proper control voltage and remains on unless a control voltage problem occurs.
  • Page 51: Settings And Adjustments

    Dip switches are factory set. Failure to maintain factory settings may adversely affect performance and warranty coverage. For more information, contact your Hoshizaki Service Center. 1. Default Dip Switch Settings The dip switches are factory-adjusted to the following positions for both the "E" and "G"...
  • Page 52: B) "G" Control Board With Harvest Pump Timer Operation

    "G" Control Board with Harvest Pump Timer Operation S4 Dip Switch S4 Dip Switch No. KM-1301SAH/3 KM-1301SWH/3 OFF OFF ON ON ON ON ON OFF OFF OFF KM-1601SAH/3 KM-1301SRH/3 OFF OFF ON ON ON ON ON OFF ON OFF...
  • Page 53: Pump-Out Timer (S4 Dip Switch 3 & 4)

    3. Pump-Out Timer (S4 dip switch 3 & 4) NOTICE On models with harvest pump timer, do not adjust 3 off and 4 on. Pump does not run in pump-out rotation in this setting. When a pump-out is called for, the pump motor stops for 2 sec., then energizes in the reverse direction, taking water from the bottom of the water tank and forcing pressure against the check valve seat allowing water to go through the check valve and down the drain.
  • Page 54: Pump-Out Frequency Control (S4 Dip Switch 5 & 6)

    4. Pump-Out Frequency Control (S4 dip switch 5 & 6) The pump-out frequency control is factory set. Generally no adjustment is required. However, where water quality is bad and the icemaker needs a pump-out more often, the pump-out frequency can be adjusted. The pump-out frequency control can be set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles.
  • Page 55: B) Harvest Pump Timer: "G" Control Board

    In this case, see "II.G.3. Low Ice Production" for possible solutions. The freeze timer is factory set and no adjustment is required. Before changing this setting, contact Hoshizaki Technical Support at 1-800-233-1940 for recommendations.
  • Page 56: Float Switch Selector (S5 Dip Switch 1): "G" Control Board

    8. Float Switch Selector (S5 dip switch 1): "G" Control Board NOTICE Do not adjust. This must be left in the factory default position or the icemaker will not operate correctly. 9. Refill Counter (S5 dip switch 2 through 5): "G" Control Board NOTICE Do not adjust.
  • Page 57: Refrigeration Circuit And Component Service Information

    IV. Refrigeration Circuit and Component Service Information WARNING • This appliance should be diagnosed and repaired only by qualified service personnel to reduce the risk of death, electric shock, serious injury, or fire. • Move the control switch to the "OFF" position and turn off the power supply. Place the disconnect in the "OFF"...
  • Page 58 2. Brazing WARNING • R-404A itself is not flammable at atmospheric pressure and temperatures up to 176°F (80°C). • R-404A itself is not explosive or poisonous. However, when exposed to high temperatures (open flames), R-404A can be decomposed to form hydrofluoric acid and carbonyl fluoride both of which are hazardous.
  • Page 59 Remember to loosen the connection and purge the air from the hose. For the required refrigerant charge, see the rating label inside the icemaker. Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets ARI Standard 700 (latest edition) be used.
  • Page 60: Component Service Information

    • The thermistor should be at the 12 o'clock position on the tube. • Smoothly fill the recessed area of the thermistor holder with high thermal conductive type sealant. Hoshizaki America part number 4A0683-01 (Silicone Heat Sink Compound 10-8108 manufactured by GC Electronics), KE-4560 RTV (manufactured by ShinEtsu Silicones), or equivalent are recommended.
  • Page 61: Water Regulating Valve Adjustment (Water-Cooled Models)

    C. Water Regulating Valve Adjustment (water-cooled models) The water regulating valve is factory set, and generally no adjustment is required. However, when necessary, adjust the water regulator using the following procedure. 1) Prepare a thermometer to check the condenser drain temperature. Attach a pressure gauge to the high-side line of the system.
  • Page 62: Maintenance

    V. Maintenance The maintenance schedule below is a guideline. More frequent maintenance may be required depending on water quality, the appliance's environment, and local sanitation regulations WARNING • Only qualified service technicians should service the appliance. • To reduce the risk of electric shock, do not touch the control switch or service switch with damp hands •...
  • Page 63: Preparing The Icemaker For Periods Of Non-Use

    VI. Preparing the Icemaker for Periods of Non-Use NOTICE • When storing the appliance for an extended time or in sub-freezing temperatures, follow the instructions below to prevent damage. • To prevent damage to the water pump, do not operate the appliance with the control switch in the "WASH"...
  • Page 64 3. On water-cooled model, remove the water from the water-cooled condenser: 1) Make sure the power supply is off, then remove the front, top, and right side panels. 2) Close the condenser water supply line shut-off valve. If connected to a closed loop system, also close the condenser return line shut-off valve.
  • Page 65: Disposal

    VII. Disposal The appliance contains refrigerant and must be disposed of in accordance with applicable national, state, and local codes and regulations. Refrigerant must be recovered by properly certified service personnel.
  • Page 66: Technical Information

    VIII. Technical Information We reserve the right to make changes in specifications and design without prior notice. A. Specification and Performance Data Pressure data is recorded at 5 min. into freezing cycle. The data not in bold should be used for reference only. 1.
  • Page 67: Km-1301Sah3

    2. KM-1301SAH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 9.5 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2220(4.6) 2090(3.9) WATER gal./24HR (gal./100 lbs.)
  • Page 68: Km-1301Swh

    3. KM-1301SWH SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral for 115V) or 208-230/60/1 AMPERAGE 8.2 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC...
  • Page 69: Km-1301Swh3

    4. KM-1301SWH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 6.1 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 1840(3.4) 1770(3.2) WATER gal./24HR (gal./100 lbs.)
  • Page 70: Km-1301Srh With Urc-14F

    5. KM-1301SRH with URC-14F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral for 115V) or 208-230/60/1 AMPERAGE 13.5A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC...
  • Page 71: Km-1301Srh3 With Urc-14F

    6. KM-1301SRH3 with URC-14F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 10.7A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2140(4.3) 2090(3.8) WATER gal./24HR (gal./100 lbs.)
  • Page 72: Km-1400Swh-M

    7. KM-1400SWH-M SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (2 Wire) AMPERAGE 9.7 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 15 A MAXIMUM FUSE SIZE 15 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 1820(3.4) 1800(3.2) POTABLE WATER gal./24HR (gal./100 lbs.)
  • Page 73: Km-1400Swh3-M

    8. KM-1400SWH3-M SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 7.1 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 15 A MAXIMUM FUSE SIZE 15 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 1720(3.3) 1700(3.0) POTABLE WATER gal./24HR (gal./100 lbs.)
  • Page 74: Km-1601Sah

    9. KM-1601SAH SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral for 115V) AMPERAGE 15.0 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2630(4.70) 2450(4.03)
  • Page 75: Km-1601Sah3

    10. KM-1601SAH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 12.0 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2610(4.65) 2370(3.91) WATER gal./24HR (gal./100 lbs.) 249(18.5) 708(48.6) ICE PRODUCTION PER CYCLE...
  • Page 76: Km-1601Swh

    11. KM-1601SWH SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral for 115V) AMPERAGE 13.4 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2410(3.8) 2300(3.7)
  • Page 77: Km-1601Swh3

    12. KM-1601SWH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 9.0 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2390(3.66) 2270(3.5) WATER gal./24HR (gal./100 lbs.) 372(23.8) 804(51.7) WATER COOLED CONDENSER...
  • Page 78: Km-1601Srh With Urc-21F Auxiliary Codes: R-0, R-1, And Some S-1

    13. KM-1601SRH with URC-21F Auxiliary Codes: R-0, R-1, and some S-1 This data applies to units with an 8 l/min water valve. The 8 l/min water valve is part number 3U0111-02 and has J248-032 stamped on the side of the valve facing the rear of the unit.
  • Page 79: Km-1601Srh With Urc-21F Auxiliary Codes: Some S-1 And S-2 And Later

    14. KM-1601SRH with URC-21F Auxiliary Codes: some S-1 and S-2 and Later This data applies to units with a 15 l/min or 11 l/min water valve. The 15 l/min water valve is part number 3U0111-01 and has J248-030 stamped on the side of the valve facing the rear of the unit.
  • Page 80: Km-1601Srh With Urc-22F Auxiliary Codes: S-2 And Later

    15. KM-1601SRH with URC-22F Auxiliary Codes: S-2 and Later This data applies to units with an 11 l/min water valve. The 11 l/min water valve is either part number 4A1176-04 or 4A5251-04 and has the part number stamped on the side of the valve facing the front of the unit. SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral for 115V)
  • Page 81: Km-1601Srh3 With Urc-21F Auxiliary Codes: R-0, R-1, And Some S-1

    16. KM-1601SRH3 with URC-21F Auxiliary Codes: R-0, R-1, and some S-1 This data applies to units with an 8 l/min water valve. The 8 l/min water valve is part number 3U0111-02 and has J248-032 stamped on the side of the valve facing the rear of the unit.
  • Page 82: Km-1601Srh3 With Urc-21F Auxiliary Codes: Some S-1 And S-2 And Later

    17. KM-1601SRH3 with URC-21F Auxiliary Codes: some S-1 and S-2 and Later This data applies to units with a 15 l/min or 11 l/min water valve. The 15 l/min water valve is part number 3U0111-01 and has J248-030 stamped on the side of the valve facing the rear of the unit.
  • Page 83: Km-1601Srh3 With Urc-22F Auxiliary Codes: S-2 And Later

    18. KM-1601SRH3 with URC-22F Auxiliary Codes: S-2 and Later This data applies to units with an 11 l/min water valve. The 11 l/min water valve is either part number 4A1176-04 or 4A5251-04 and has the part number stamped on the side of the valve facing the front of the unit. SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3...
  • Page 84: Km-1900Sah

    19. KM-1900SAH SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral 115V) AMPERAGE 14.4 A (5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2670(4.1)
  • Page 85: Km-1900Sah3

    20. KM-1900SAH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 8.59 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2610(4.1) 2510(3.2) WATER gal./24HR (gal./100 lbs.) 260(17.0) 548(29.5) ICE PRODUCTION PER CYCLE...
  • Page 86: Km-1900Swh

    21. KM-1900SWH SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral 115V) AMPERAGE 12.5 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2390(3.1) 2330(3.0) POTABLE WATER gal./24HR (gal./100 lbs.)
  • Page 87: Km-1900Swh3

    22. KM-1900SWH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 8.4 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2490(3.3) 2410(3.2) POTABLE WATER gal./24HR (gal./100 lbs.) 341(18.8) 584(32.0) WATER COOLED CONDENSER...
  • Page 88: Km-1900Srh With Urc-21F

    23. KM-1900SRH with URC-21F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral 115V) AMPERAGE 14.9 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2630(3.9)
  • Page 89: Km-1900Srh With Urc-22F

    24. KM-1900SRH with URC-22F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral 115V) AMPERAGE 14.9 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2790(4.09)
  • Page 90: Km-1900Srh3 With Urc-21F

    25. KM-1900SRH3 with URC-21F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 11.0 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2840(4.1) 2680(3.3) WATER gal./24HR (gal./100 lbs.)
  • Page 91: Km-1900Srh3 With Urc-22F

    26. KM-1900SRH3 with URC-22F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 11.0 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2780(4.04) 2640(3.33) WATER gal./24HR (gal./100 lbs.) 345(20.9)
  • Page 92: Km-2100Swh3

    27. KM-2100SWH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 10.5 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2860(3.35) 2740(3.14) POTABLE WATER gal./24HR (gal./100 lbs.) 410(20.0) 673(32.1) WATER COOLED CONDENSER...
  • Page 93: Km-2100Srh3 With Urc-22F

    28. KM-2100SRH3 with URC-22F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 12.5 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 3210(4.26) 2900(3.42) WATER gal./24HR (gal./100 lbs.) 382(21.1)
  • Page 94: Km-2500Swh3

    29. KM-2500SWH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 14.2 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 3720(3.78) 3510(3.5) WATER gal./24HR (gal./100 lbs.) 459(19.4) 744(30.9) WATER COOLED CONDENSER...
  • Page 95: Km-2500Srh3 With Urc-23F

    30. KM-2500SRH3 with URC-23F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 17.7 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 4190(4.5) 3780(3.7) WATER gal./24HR (gal./100 lbs.) 416(18.6)
  • Page 96: Kmh-2000Swh

    31. KMH-2000SWH SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral 115V) AMPERAGE 12.1 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2420(3.3) 2410(3.2) POTABLE WATER gal./24HR (gal./100 lbs.)
  • Page 97: Kmh-2000Swh3

    32. KMH-2000SWH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 7.7 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2330(3.2) 2280(2.9) POTABLE WATER gal./24HR (gal./100 lbs.) 296(17.1) 540(29.0) WATER COOLED CONDENSER...
  • Page 98: Kmh-2000Srh With Urc-22F

    33. KMH-2000SRH with URC-22F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral 115V) AMPERAGE 14.9 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2680(3.8)
  • Page 99: Kmh-2000Srh3 With Urc-22F

    34. KMH-2000SRH3 with URC-22F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 9.9 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2600(3.7) 2430(3.0) WATER gal./24HR (gal./100 lbs.) 281(16.8)
  • Page 100: Wiring Diagrams

    B. Wiring Diagrams 1. "E" and "G" Control Board Schematics without Harvest Pump Timer Relays a) KM-1601SWH, KM-1601SRH, KM-1900S_H, KMH-2000S_H...
  • Page 101: B) Km-1601Swh3, Km-1601Srh3, Km-1900S_H3, Km-2100S_H3

    b) KM-1601SWH3, KM-1601SRH3, KM-1900S_H3, KM-2100S_H3, KM-2500S_H3, KMH-2000S_H3...
  • Page 102: G" Control Board Schematics With Harvest Pump Timer Relays

    2. "G" Control Board Schematics with Harvest Pump Timer Relays a) KM-1301S_H T-0, U-0...
  • Page 103: B) Km-1301S_H U-1 To D-0

    b) KM-1301S_H U-1 to D-0...
  • Page 104: C) Km-1301Sah And Km-1301Swh D-1 To E-1

    c) KM-1301SAH and KM-1301SWH D-1 to E-1...
  • Page 105: D) Km-1301Srh D-1 To E-0

    d) KM-1301SRH D-1 to E-0...
  • Page 106: E) Km-1301Srh E-1 And Later

    e) KM-1301SRH E-1 and Later...
  • Page 107: F) Km-1400Swh-M

    f) KM-1400SWH-M...
  • Page 108: G) Km-1601Sah E-0 And Earlier

    g) KM-1601SAH E-0 and Earlier...
  • Page 109: H) Km-1601Sah E-1 And Later

    h) KM-1601SAH E-1 and Later...
  • Page 110: I) Km-1301S_H3 T-0, U-0

    i) KM-1301S_H3 T-0, U-0...
  • Page 111: J) Km-1301S_H3 U-1 To E-0 And Km-1601Sah3 A-0 To E-0

    j) KM-1301S_H3 U-1 to E-0 and KM-1601SAH3 A-0 to E-0...
  • Page 112: K) Km-1301S_H3 E-1 And Km-1601Sah3 E-1 And Later

    k) KM-1301S_H3 E-1 and KM-1601SAH3 E-1 and Later...
  • Page 113: L) Km-1400Swh3-M

    l) KM-1400SWH3-M...