Additional Charge Calculation - Fujitsu AR*G60LHTA Design & Technical Manual

Air conditioner duct type, refrigerant r410a inverter, indoor/outdoor
Hide thumbs Also See for AR*G60LHTA:
Table of Contents

Advertisement

9.

ADDITIONAL CHARGE CALCULATION

MODEL :
AOG60LATT
Refrigerant type
Refrigerant amount
IF ADDITIONAL REFRIGERANT IS REQUIRED
When the piping is longer than chargeless piping length, additional charging is necessary.
For the additional amount, see the table below.
Additional charging amount
L1
L1 > Chargeless piping length
Refrigerant pipe size
[mm (in.)]
Piping length
Liquid
9.52 (3/8)
Gas
15.88 (5/8)
Piping length
Liquid
9.52 (3/8)
Gas
19.05 (3/4)
Piping length
Liquid 12.70 (1/2)
15.88 (5/8)
Gas
19.05 (3/4)
R410A
g
3,450
H1
Additional charging amount [g]
30 m or less 40 m
50 m
None
500
1,000 1,500 2,000
30 m or less 40 m
50 m
None
500
1,000
15 m or less 25 m
35 m
None
1,000 2,000
- (02 - 11) -
Rate
[g/m]
60 m
70 m
50
50
100