6-2.
HEATING CAPACITY
This table is created using the rated capacity.
MODEL
: ARG60LHTA
AFR
59.2
°CDB
°CDB
°CWB
-15
-10
-5
0
5
7
10
15
20
24
3
AFR: Air Flow Rate ( m
/min)
TC : Total Capacity (kW)
IP : Input Power (kW)
16
TC
IP
-16
13.17
5.18
12.86
-11
14.64
5.18
14.29
-7
16.23
5.18
15.85
-2
17.48
5.19
17.06
3
18.84
5.20
18.39
6
18.90
4.94
18.45
8
20.74
4.62
20.25
10
22.28
4.58
21.75
15
21.63
4.51
21.12
18
19.91
3.75
19.43
Indoor temperature
18
20
TC
IP
TC
IP
5.29
12.55
5.40
5.29
13.95
5.40
5.29
15.46
5.40
5.30
16.64
5.41
5.31
17.94
5.42
5.05
18.00
5.15
4.71
19.76
4.81
4.68
21.22
4.77
4.60
20.60
4.69
3.83
18.96
3.91
- (01 - 11) -
22
24
TC
IP
TC
IP
12.23
5.51
11.92
5.62
13.60
5.51
13.25
5.62
15.07
5.51
14.69
5.62
16.23
5.52
15.81
5.63
17.49
5.53
17.05
5.64
17.55
5.25
17.10
5.36
19.26
4.91
18.77
5.00
20.69
4.87
20.16
4.94
20.09
4.79
19.57
4.86
18.48
3.99
18.01
4.05