Displacement ventilation or single zone variable airflow rooftop units single package, electric cool, gas heating with puron refrigerant and comfortlink controls
Hide thumbs Also See for 48PD05:

Advertisement

NOMINAL
VOLTAGE
48PD
POWER
RANGE
UNIT
SUPPLY
SIZE
V-Ph-Hz
Min
Max
208/230-3-60
187
253
O5
460-3-60
414
506
208/230-3-60
187
253
06
460-3-60
414
506
Table 8 - Electrical
Data - Units Without
Optional
Convenience
Outlet
COMPRESSOR
OFM
COMBUST
IFM
POWER SUPPLY
FAN
Conv
PWR
FLA
MOTOR
Outlet
EXH
RLA
LRA
Qty
(ca)
FLA
FLA
TYPE
FLA
MCA
MOCPI-
STD
5.2
26.3/26.3
40/40
ALT
5.2
26.3/26.3
40/40
16.1
110
1
1.0
0.52
none
STD
5.2
27.7/27.7
40/40
1.4
ALT
5.2
27.7/27.7
40/40
STD
2.6
10.9
15
ALT
2.6
10.9
15
6.2
52
1
0.5
0.30
none
STD
2.6
11.5
15
0.6
ALT
2.6
11.5
15
STD
5.2
29.1/29.1
45/45
ALT
5.2
29.1/29.1
45/45
17.9
110
1
1.5
0.52
none
STD
5.2
30.5/30.5
45/45
1.4
ALT
5.2
30.5/30.5
45/45
STD
2.6
13.2
20
ALT
2.6
13.2
20
7.8
52
1
0.8
0.30
none
STD
2.6
13.8
20
0.6
ALT
2.6
13.8
20
DISCONNECT
SIZE
FLA
LRA
26/26
142/142
26/26
142/142
27/27
144/144
27/27
144/144
11
68
11
68
11
69
11
69
28/28
143/143
28/28
143/143
30/30
145/145
30/30
145/145
13
69
13
69
14
70
14
70
Table 9 - Electrical
Data
- Units With
Optional
Convenience
Outlet
NOMINAL
VOLTAGE
48PD
POWER
RANGE
UNIT
SUPPLY
SIZE
V-Ph-Hz
Min
Max
208/230-3-60
187
253
O5
460-3-60
414
506
208/230-3-60
187
253
06
460-3-60
414
506
COMPRESSOR
OFM
COMBUST.
IFM
POWER SUPPLY
FAN
Conv
PWR
FLA
MOTOR
Outlet
EXH
RLA
LRA
Qty
(ca)
FLA
FLA
TYPE
FLA
MCA
MOCPI
STD
5.2
31.1/31.1
45/45
ALT
5.2
31.1/31.1
45/45
16.1
110
1
1.0
0.52
YES
STD
5.2
32.5/32.5
45/45
1.4
ALT
5.2
32.5/32.5
45/45
STD
2.6
13.1
15
ALT
2.6
13.1
15
6.2
52
1
0.5
0.30
YES
STD
2.6
13.7
20
0.6
ALT
2.6
13.7
20
STD
5.2
33.9/33.9
50/50
ALT
5.2
33.9/33.9
50/50
17.9
110
1
1.5
0.52
YES
1.4
STD
5.2
35.3/35.3
50/50
ALT
5.2
35.3/35.3
50/50
-
STD
2.6
15.4
20
ALT
2.6
15.4
20
7.8
52
1
0.8
0.30
YES
0.6
STD
2.6
16.0
20
ALT
2.6
16.0
20
DISCONNECT
SIZE
FLA
LRA
31/31
147/147
31/31
147/147
33/33
149/149
33/33
149/149
13
70
13
70
14
71
14
71
34/34
148/148
34/34
148/148
35/35
150/150
35/35
150/150
15
71
15
71
16
72
16
72
LEGEND
FLA
-
Full Load Amps
HACR
-
Heating,
Air Conditioning
and Refrigeration
IFM
-
Indoor
(Evaporator)
Fan Motor
LRA
-
Locked
Rotor Amps
MCA
-
Minimum
Circuit Amps
MOCP
-
Maximum
Overcurrent
Protection
NEC
-
National
Electrical
Code
OFM
-
Outdoor
(Condenser)
Fan Motor
RLA
-
Rated Load Amps
t
Fuse or Breaker
NOTES:
1.
In compliance
with
NEC
requirements
for muttimotor
and
combination
toad
equipment
(refer
to NEC Articles
430
and 440),
the
overcurrent
protective
device
for the
unit shall
be fuse
or
HACR
breaker.
Canadian
units
may
be fuse
or circuit
breaker.
2.
Unbalanced
3-Phase
Supply
Voltage
Never
operate
a motor
where
a phase
imbalance
in supply
voltage
is greater
than
2%.
Use
the following
formula
to determine
the percentage
of voltage
imbalance.
% Voltage
Imbalance
= 100 x
max
voltage
deviation
from
average
voltage
average
voltage
Example:
Supply
voltage
is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average
Voltage
=
224
+ 231
+ 226
3
681
3
227
Determine
maximum
deviation
from
average
voltage.
(AB) 227
224
= 3 v
(BC)
231
227
= 4 v
(AC)
227
226
= 1 v
Maximum
deviation
is 4 v.
Determine
percent
of voltage
imbalance.
4
% Voltage
Imbalance
= 100 x
227
= 1.76%
This amount
of phase
imbalance
is satisfactory
as it is below
the
maximum
allowable
2%.
IMPORTANT:
If the
supply
voltage
phase
imbalance
is more
than
2%, contact
your
local
electric
utility
company
immediately.
15