Download Print this page

Carrier 48PD05 Installation Instructions Manual page 13

Displacement ventilation or single zone variable airflow rooftop units single package, electric cool, gas heating with puron refrigerant and comfortlink controls
Hide thumbs Also See for 48PD05:

Advertisement

Step 9 -- Make
Electrical
Connections
Field Power Supply
(For more
details,
refer to the Controls,
Start-Up,
Operation,
and
Troubleshooting
manual).
All 208/230v
units are factory wired for 230v power
supply.
If the
208/230v
unit
is to be connected
to a 208v
power
supply,
the
transformers
(TRANI
and TRAN2)
must
be rewired
by moving
the black
wire with
the l/4-in,
female
quick
connector
from the
230volt
connection
and
moving
to
the
200volt
l/4-in,
male
terminal
on the primary
side of the transformer.
Refer
to unit label diagram
for additional
information.
Leads
are
provided
for
field
wire
connections.
Use
UL
(Underwriters
Laboratories)
approved
copper/aluminum
connector.
When
installing
units,
provide
safety
disconnect
per
NEC
(National
Electrical
Code)
Article
440
or
local
codes.
For
non-fused
disconnects,
size disconnect
according
to the sizing data
provided
in the electrical
data tables.
If a fused disconnect
is used,
determine
the minimum
size for the switch based on the disconnect
sizing
data
provided
in
the
electrical
data
tables
and
then
coordinate
the
disconnect
housing
size
to
accommodate
the
Maximum
Overcurrent
Protection
(MOCP)
device
size as marked
on the unit informative
plate. (See Table 9 and 10.)
All field wiring
must comply
with NEC and local codes. Size wire
based on MCA
(Minimum
Circuit
Amps)
on the unit informative
plate. See Fig. 12 for power wiring
connection
to the unit leads and
equipment
ground.
Route power
and ground
lines through
control
box
end panel
or
unit basepan
(see Fig. 2) to connections
as shown
on unit wiring
diagram
and Fig. 12. Factory
leads may be wired
directly
to the
disconnect.
[]NIT
DAMAGE
HAZARD
Failure
to follow
this caution
may
result
in equipment
damage.
The correct
power
phasing
is critical to the operation
of the
scroll
compressors.
An
incorrect
phasing
will
result
in
alarm
being
generated
and compressor
operation
lockout.
Should
this occur, power
phase correction
must be made to
the incoming
power.
ELECTRICALSHOCK
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury or death.
Unit
cabinet
must
have
an
uninterrupted,
unbroken
electrical
ground
to minimize
the possibility
of personal
iniury if an electrical
fault should
occur.
This ground
may
consist
of electrical
wire
connected
to unit ground
lug in
control
compartment,
or conduit
approved
for electrical
ground
when
installed
in accordance
with
NEC;
ANSI
(American
National
Standards
Institute)/NFPA
(National
Fire
Protection
Association),
latest
edition,
and
local
electrical
codes.
Do
not use gas piping
as an electrical
ground.
Field wiring
must conform
to temperature
limitations
for type "T"
wire.
All
field
wiring
must
comply
with
NEC
and
local
requirements.
Operating
voltage
to compressor
must
be within
voltage
range
indicated
on unit nameplate.
On 3-phase
units, voltages
between
phases must be balanced
within
2%.
[]nit
failure
as a result
of operation
on improper
line voltage
or
excessive
phase
imbalance
constitutes
abuse
and
may
cause
damage
to electrical
components.
On"
oLU
----I
I
FIELD
I
POWER
I
WIRING
r
I
I
I-
I
I
POWER
C.A1
EQUIP GND
LEGEND
C.A1
-- Compressor
Contactor
(A1)
EQUIP
-- Equipment
GND
-- Ground
NEC
-- National
Electrical
Code
NOTE: The maximum
wire size for C.A1 is 2/0.
Fig. 12 - Field Power
Wiring
Connections
C06237
Field
Control
Wiring
Unit
can be controlled
with
a Carrier-approved
accessory
space
temperature
sensor.
Install
sensor
according
to the installation
instructions
included
with
accessory.
Locate
space
temperature
sensor
on a solid
interior
wall in the conditioned
space
to sense
average
temperature.
The 48PD
unit is not compatible
with
a
conventional
YI/WI
thermostat.
NOTE:
Use 20 AWG (American
Wire Gauge)
wire to connect
the
sensor
to the controller.
The wire is suitable
for distances
of up to
500
ft.
Use a three-conductor
shielded
cable for the sensor
and
set-point
adjustment
connections.
The
standard
CCN
communication
cable
can be used.
If the
set-point
adjustment
(slide
bar) is not required,
then
an unshielded,
18 or 20 AWG
(American
Wire Gauge),
two-conductor,
twisted
pair cable can be
used.
Route space
temperature
sensor
cable or equivalent
single leads of
colored
wire from
sensor
terminals
through
conduit
into unit to
low-voltage
connections
as shown
on unit label
wiring
diagram
and in Fig. 13.
g
13

Advertisement

loading

This manual is also suitable for:

48pd06