6 Motion Control Programming
Editing a Cam Data Variable on the Computer after Editing It from
the User Program
If you edit or overwrite a cam data variable from the user program and then use the MC_SaveCam-
Table instruction to save the cam table to non-volatile memory, you cannot edit the data with the Cam
Editor of the Sysmac Studio. This section describes how to use spreadsheet software to edit the data
and then use it as a cam table.
Transfer Cam Table [Controller to File]:
Uploads the cam table from the Controller and saves it in a CSV file.
Transfer Cam Table [File to Controller]:
Downloads the cam table from a CSV file to the Controller.
Sysmac Studio
Upload
* Use the Synchronization menu command of the Sysmac Studio to upload and download the project.
 Saving a Cam Table from Non-volatile Memory to a CSV File
• Right-click a cam profile that you edited in the Cam Data Settings of the Sysmac Studio and select
Transfer Cam Table [Controller to File] from the menu.
• The Save Dialog Box is displayed. Enter the file save location and file name, and then click the
Save Button.
 Editing CSV Files
• Use spreadsheet software or other CSV-compatible software to edit the CSV file.
 Transferring the CSV File to the CPU Unit
• Right-click the cam profile to download and select Transfer Cam Table [File to Controller] from
the menu.
• The Open File Dialog Box is displayed. Specify the file to transfer, and then click the OK Button.
• To enable the cam table that you transferred, reset the Controller or cycle the power supply to the
Controller after the cam table is transferred.
Precautions for Correct Use
Precautions for Correct Use
• Synchronize the data with the Controller before you transfer a cam table from a file to the Con-
troller.
• If you transfer the cam table to the Controller during a synchronization operation after you
transfer a cam table from a file to the Controller, the cam table in the Controller is replaced with
the data in the Cam Data Settings. Either transfer the cam data from the file to the Controller
again, or do not include the Cam Data Settings in the synchronization data.
6-38
Save/Export
Read/Import
Download
9
DC24V
7mA
Edit
CSV file
NJ/NX-series CPU Unit Motion Control User's Manual (W507)
Spreadsheet
software

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx102-1Nx102-90Nj501Nj301-1Nx1p2-1Nx1p2-90 ... Show all

Table of Contents