TRUE
TAC-27K / TAC-27K-HC-LD: AIR CURTAIN
THE INTERVAL BETWEEN DEFROST
TERMINATION IS THE TIME BETWEEN
EACH DEFROST CYCLE.
NOTE: This interval is started when the cabinet is plugged in
or after initiate of manual defrost.
HOW TO SEE "idF" INTERVAL
BETWEEN DEFROST:
STEP 1 - Press and hold the (SET) and (DOWN)
arrows at the same time for (7-12) seconds.
STEP 2 - You should then see (HY).
STEP 3 - Release the keys.
STEP 4 - Press the down arrow until you see the
letters "idF".
STEP 5 - Press the (SET) button. You should see the
number 6. This is time in hours between each defrost
cycle. To change, press the (UP / DOWN) arrow to
set a new number and then push the (SET) button
to save these changes. Wait 10 seconds for control to
display temperature.
NOTE: The interval between defrost termination is
the time between each defrost cycle.
THE PROGRAM PARAMETERS CAN BE
DOWNLOADED BY THE USE OF A "HOT KEY."
NOTE: These parameters will vary from model to model.
HOW TO DOWNLOAD
THE CONTROL PARAMETER:
STEP 1 - Turn controller in the off position or unplug
cabinet.
STEP 2 - Insert "Hot Key" into the back of the controller.
STEP 3 - Turn on controller or plug in cabinet.
STEP 4 - "Hot Key" will download automatically once
download is complete. Remove "Hot Key".
Dixell Control XW60VS
1
The program parameters can be downloaded by the
use of a "Hot Key." THESE PARAMETERS WILL VARY FROM
MODEL TO MODEL.
Dixell Control XW60VS
1
.
.
www
truemfg
com
Dixell Control XW60VS
12