8.4.15 Room Temperature Thermistor in Remote Controller Abnormality

CJ
Error Code
Applicable
All indoor models
Models
Method of Error
Error detection is carried out by temperature detected by room temperature thermistor in remote
controller
Detection
Error Decision
When the room temperature thermistor in remote controller becomes disconnected or shorted
while the unit is running.
Conditions
∗ Error code is displayed but the system operates continuously.
Supposed
Causes
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Clear the malfunction code history.
(∗1)
CJ
Is "
remote controller?
Note:
∗1. How to delete "the record of error codes".
Press the "Operate/ Stop" button for 4 seconds and more while the error code is displayed in the
inspection mode.
CONVENI-PACK
Defective remote controller thermistor
Defective remote controller PCB
YES
" displayed on the
NO
Troubleshooting
Replace the remote controller.
External factor other than
equipment error.
(for example, noise etc.)