Outline of Functions (Outdoor unit)
(2) Capacity control
Tst_BU: Target evaporative temperature
Tsd_BU: Evaporative temperature set by DIP switch
Tsp1_BU: Temperature correction setting 1 by the BS button
Tsp2_BU: Temperature correction setting 2 by the BS button
Tst_BU = Tsd_BU +
Refer to the "Field setting" for details.
103
Tsp1_BU +
A3P side
Tsd_BU (Lpmd_BU)
ON
OFF
1
2
3
4
(Factory setting)
ON
OFF
1
2
3
4
ON
OFF
1
2
3
4
ON
OFF
1
2
3
4
Tsp2_BU
ON
-35°C
OFF
(0.118MPa)
ON
-45°C
OFF
(0.029MPa)
Tsd_BU: Evaporative temperature set by DIP
Lpmt_BU: Pressure conversion of target
-40°C
(0.069MPa)
-30°C
(0.167MPa)
SiBE811001EB
A3P side
Tsd_BU (Lpmd_BU)
-25°C
(0.225MPa)
1
2
3
4
-20°C
(0.294MPa)
1
2
3
4
switch
evaporating temperature