4

Installation

4.1

Opening the units

4.1.1

To open the outdoor unit

DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
2
4.1.2
To open the switch box cover of the
outdoor unit
4.2

Mounting the outdoor unit

4.2.1

To provide the installation structure

Prepare 6 sets of anchor bolts, nuts and washers (field supply) as
follows:
EBLQ+EDLQ011~016CAV3+W1
Daikin Altherma low temperature monobloc
4P522031-1 – 2018.01
7
6× M12
(mm)
a
Make sure not to cover the drain holes.
INFORMATION
The recommended height of the upper protruding part of
the bolts is 20 mm.
NOTICE
Fix the outdoor unit to the foundation bolts using nuts with
resin washers (a). If the coating on the fastening area is
stripped off, the nuts rust easily.
a
4.2.2

To install the outdoor unit

6× M12
4.2.3

To provide drainage

Make sure that condensate can be evacuated properly. When the
unit is in cooling mode, condensate may also form in the hydro part.
When providing drainage, therefore make sure to cover the entire
unit.
4 Installation
a
Installation manual
7