RTD TempeRaTuRe sensoR foR ambienT sensing insTallaTion insTRucTions
WARNING:
This component is an electrical device. It must be installed
correctly to ensure proper operation and to prevent shock or
fire. Read these important warnings and carefully follow all the
Thermal Building &
indusTrial heaT Tracing soluTions
RTD-200
installation instructions. Component approvals and performance
are based on the use of s pecified parts only. Do not use substitute
parts or vinyl electrical tape to make connections.
EN-RaychemRTD200-IM-H56998      04/16
Description
The RTD-200 is a three-wire platinum RTD (resistance-
temperature-detector) typically used with electronic control
systems that require accurate ambient temperature sensing.
The RTD-200 comes with a 1/2" NPT fitting that installs to the
appropriate conduit box. This allows mounting of the RTD in a
typical ambient location. This also allows for splicing of RTD
extension wire back to the controller.
tools requireD
None
ADDitionAl MAteriAls requireD
None
Kit contents
qty
Description
1
RTD temperature sensor with 1/2-in NPT fitting

specificAtions

sensor
Housing
316 stainless steel
Dimensions
3 in (7.6 mm) length 1/4 in (6 mm)
diameter
Accuracy
±0.3°F (0.2°C)
Range
–100°F to 300°F (–73°C to 149°C)
Resistance
100 ohms +/– .25 ohm at 0°C
X=0.00385 ohms/ohm/°C
extension Wires
Wire size (each of 3)
22 AWG
Wire dielectric strength
600 volts
Length
6 ft (1.8 m)
Outer jacket
Fluoropolymer
Maximum exposure
300°F (149°C)
temperature
Sensor fitting
1/2-in NPT with sealing washer and nut
Approvals
Approvals associated with control
device, however not to be used in
Div. 1 areas.
1 / 2
1 / 2

Advertisement

loading

Summary of Contents for Pentair Raychem RTD-200

  • Page 1: Specifications

    RTD-200 RTD TempeRaTuRe sensoR foR ambienT sensing insTallaTion insTRucTions Description The RTD-200 is a three-wire platinum RTD (resistance- temperature-detector) typically used with electronic control systems that require accurate ambient temperature sensing. The RTD-200 comes with a 1/2” NPT fitting that installs to the appropriate conduit box.
  • Page 2 Fax: +1.650.474.7711 thermal.info@pentair.com Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. © 2003-2016 Pentair. PN P000000095 Thermal Building &...