Altering the Time Program for the DHW Recirculation Pump

Automatic?
1Time prog. DHW recirc.
1pump
1---7
1
1---7
The time program consists of 4 timer cycles. Cycle 1 is preset at the factory from
06:00 to 22:00 hrs, i.e. the DHW recirculation pump is on during this period.
The automatic mode is also selected, i.e. the DHW recirculation pump runs parallel
to the domestic hot water heating time program.
You have the following options to set the timer cycles to suit your requirements:
By setting the corresponding timer cycles, the DHW recirculation pump can be
switched on and off up to 4 times per day.
You can set identical timer cycles for every day of the week or individual timer
cycles for each day of the week.
The DHW recirculation pump should run at those times when you require hot water.
Please see the note headed "Important" on page 16.
When timer is programmed with --:--, DHW recirculation pump is off.
When timer is programmed with ON 00:00, OFF 24:00, DHW recirculation pump
operates continuously.
Identical DHW recirculation pump cycles for every day of the week
1. Open the hinged cover on the
programming unit.
2.
for "DHW recirc.
pump time program".
Wait until the display
shown on the left appears.
3.
for "Individual?".
4.
to confirm.
5.
for "DHW recirc.
pump cycle 1".
for "DHW recirc.
6.
pump cycle 1 ON".
7.
/
to enter the start of the
cycle.
8.
to confirm; the display
changes to "DHW recirc.
pump cycle 1 OFF".
9.
/
to enter the end of the
cycle.
10.
to confirm; the display
changes to "DHW recirc.
pump cycle 2 ON".
11. To set the start and end of the DHW
recirculation pump cycles 2 to 4,
follow the procedure described in
points 5 to 10.
12. Close the hinged cover on the
programming unit.
To scan the timer cycles
Follow the procedure described above,
but without using the
buttons.
The DHW recirculation pump cycles at a
glance
1. Open the hinged cover on the pro-
gramming unit.
2. Press
and
simultaneously; the
preset time cycles appear on a time
slot graphic.
3. Close the hinged cover on the
programming unit.
If you wish to exit the time program
setting mode, press
Press
After you have confirmed the last
input with
and shows the boiler water
temperature.
and
DHW Production
again.
to skip a timer cycle.
, the display changes
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitotronic 300 kw3

Table of Contents