3. OUTDOOR UNIT INSTALLATION

3.3 SPACE REQUIREMENT FOR OUTDOOR UNIT

Single Unit Installation
(Wall or obstacle)
Air inlet
>30cm
N
Air inlet
Air outlet
M
Parallel connect the two units or above
>30
>60
>200

3.4 INSTALL THE OUTDOOR UNIT

Before installation, check strength and horizontality of the base so that abnormal sound does not
generate.
Fix the base firmly with anchor bolts (M10) to prevent it from collapsing.
Install the foundation and vibration-proof rubbers to directly support the bottom surface of the fixing
leg that is in contact with the bottom plate of the outdoor unit.
Mortar Hole (Φ100mm x Depth 150mm)

3.5 INSTALL THE DRAIN PIPE FOR OUTDOOR UNIT

Connect the drain outlet with an extension drain hose
Fit the gasket onto drain outlet.
Insert the drain outlet into the base pan hole of outdoor unit, and rotate 90 degree to securely assemble
them.
Maintain channel
>60cm
P
Parallel connect the front with rear sides.
unit:cm
>200
Outdoor unit
Vibration-proof rubber
Anchor bolt (M10)
≥100mm
Drainage (Wide 100mm x Depth 150mm)
Base pan hole
of outdoor unit
Gasket
Drain Outlet
Drain hose
(Field supply)
Fix with bolt
>50
>300
>300
unit:cm
>30
GB-10