No.
Name
1)
LED (Continued)
Station No. setting
switch
(A1SJ71AP23Q/
A1SJ71AR23Q)
2)
(A1SJ71AT23BQ)
Tens
place
Ones
place
Mode setting switch
(A1SJ71AP23Q/
A1SJ71AR23Q)
(A1SJ71AT23BQ)
3)
Table 4.1 Part names and settings (Continued)
TIME
DATA
UNDER
ON (OFF
if normal)
UND.
F.LOOP
R.LOOP
Sets station No. of the local module. (Factory default setting: 1)
• A1SJ71AP23Q/A1SJ71AR23Q
1 to 64: Station No.
Tens
place
(If other than above is set, the local module goes into offline
status (X0=ON).)
Ones
place
• A1SJ71AT23BQ
1 to 31: Station No.
(If other than above is set, the local module goes into offline
status (X0=ON).)
Sets operation mode. (Factory default setting: 0)
No.
0
Online
1
Online
2
Offline
3
-
4
-
Station-to-station
5
test (Executing
station)
Station-to-station
6
test (Other station)
7
Self-loopback test
8 to F
-
Description
Data link monitoring time is over.
The data of error code has been received.
Internal processing of send data is not
executed constantly.
Receive error at forward loop side
Receive error at reverse loop side
Item
Data link (with automatic return
function)
Data link (without automatic
return function)
Disconnects host station.
Unusable (If set, the local
module goes into offline status
(X0=ON).)
Checks a line between two
adjacent stations.
Checks the hardware including
transmission circuit in a single
local module.
Unusable (If set, the local
module goes into offline status
(X0=ON).)
11
Description