PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D
Menu / parameter
Value range
Easy Setup (continued)
Autoadjust Mode
Full, Controller, Valve Range,
Zero, Locked
Start Autoadjust
Start
Description
Use this parameter to define the mode or scope of the Auto Adjust function.
Full: Complete automatic adjustment
Controller: Determine control parameters only
Zero: Determine the 0 % position only
Valve Range: Determine stops only
Locked: Automatic adjustment blocked
Note
On valves where slip-stick effect is significant, valve vibration can be reduced by increasing the value of
the 'Zone' parameter.
The following values are determined during Auto Adjust:
Direction of action of the actuator
Direction of action of the reset spring
Actuator travel of the actuator / final control element
Stroke time for both directions
Control parameters
Offset for the I/P module
Static friction of the actuator / final control element
Dynamic friction of the actuator / final control element
51