... 7 Installation
... Electrical connections
Connection to device - EDP300 Control Unit for remote position sensor
M 20 mm /
NPT
1/2"
3
1 Terminals for remote position sensor
2 Remote position sensor
Figure 24: Connection of EDP300 Control Unit with remote position sensor (example)
Change from one to two columns
With the EDP300 designed for remote position sensors, the
positioner is supplied without a position sensor.
The EDP300 Control Unit contains the electronics and
pneumatics along with the following options (where applicable):
•
Analog position feedback
•
Digital position feedback
•
Emergency shutdown module
•
Universal input
Any position sensor (4 to 80 k ) may be connected.
M 20 mm /
NPT
1/2"
1
4
3
3 EMC Cable gland
4 Shielded connection cable
Cable specification
To connect the EDP300 Remote Sensor, a cable with the
following specifications needs to be used:
•
3-wire, cross-section 0.5 to 1.0 mm²
•
shielded, with at least 85 % coverage
•
Temperature range up to at least 100 °C (212 °F)
The cable glands used must also be approved for a temperature
range up to at least 100 °C (212 °F). The cable glands require a
mounting for the shielding and strain relief for the cable in
addition.
ABB offers suited cables and cable glands with DNV_GL
certification for the EDP300 Remote Version.