50
PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D
... 9 Operation

Parameter descriptions

Menu Easy Setup

Menu / parameter
Value range
Easy Setup
Language
English, Deutsch, Français,
Italiano, Español, Português
Actuator Type
Linear, Rotary
Bolt Position
Bolt On Lever, Bolt On Stem
Vent Position
Position 0%, Position 100%
Tight Shut 0%
0.0 to 45.0
Control at 0%
On, Off
Tight Shut 100%
55.0 to 100.0
Control at 100%
On, Off
DB Approach
Fast, Medium, Slow
Dead Band Calc.
Active, inactive
Description
Selects the menu language
Use this parameter to configure the positioner for operation on a linear actuator (sensor range ±30°) or
on a rotary actuator (sensor range ±45°). No mechanical modifications to the positioner are required.
Note
After changing the actuator type, it is recommended that you run Auto Adjust to prevent linearity errors.
For the linearization, when attaching to linear actuators, a differentiation is made concerning the
mechanical part of the position transfer to which the bolt is permanently mounted.
Bolt On Lever (actuator bolt on the potentiometer lever)
Bolt On Stem (actuator bolt on the valve stem)
Factory setting: Bolt On Lever
Use this parameter to specify which position is to be shown in the display when output 1 of the
positioner is completely vented.
The shut-off value is a percentage of the working range from which the 0 % position is approached.
Once the specified position limit value is reached, the actuator moves into the 0% end position.
Use this parameter to set the end position behavior. If the parameter is activated, the 0 % position is
controlled. Otherwise, the actuator moves into the 0 % mechanical end position.
The shut-off value is a percentage of the working range from which the 100 % position is approached.
Once the specified position limit value is reached, the actuator moves into the 100 % end position.
Use this parameter to set the end position behavior. If the parameter is activated, the 100 % position is
controlled. Otherwise, the actuator moves into the 100 % mechanical end position.
This parameter specifies the speed at which the dead band is approached.
In rare cases, overshooting can occur when the valve position
is being compensated. This can be prevented by reducing the speed of
the dead-band approach (DB approach).
Use this function to activate / deactivate the control behavior on the dead band.