3.1 Applicable Cable and Terminal Tightening Torque
The size of the terminal screws is M3.
The end disposal of the cable shows below.
Tighten the terminal to a torque of 0.5 to 0.8N
m.
Do not tighten terminal screws with a torque outside the abovementioned range.
Failure to do so may cause equipment failures or malfunctions.
• When one wire is connected to one terminal
Terminal
Crimp
φ3.2 (0.13")
screw
terminal
6.2 mm (0.24")
or less
φ3.2 (0.13")
6.2 mm (0.24")
Terminal
or less
• When two wires are connected to one terminal
φ3.2 (0.13")
Terminal
Crimp
6.2 mm (0.24")
screw
terminal
or less
6.3 mm (0.25")
or more
φ3.2 (0.13")
6.2 mm (0.24")
Terminal
or less
6.3 mm (0.25")
or more
3.2 Power Supply Wiring
For the power supply wiring, refer to the following manual.
→ Refer to the FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
Series User's Manual
- Analog Control Edition
3.3 Wiring of Analog Input
→ For the terminal layout, refer to Subsection 1.2.2
External power
FX
-4AD
3U
supply wiring
24+
24V DC *1
24-
Grounding
(Ground resistance:
100Ω or less)
*2
Using current input
ch
Shield *3
6.8kΩ
V+
250Ω
*4
I+
VI-
200kΩ
FG
*2
Using voltage input
ch
6.8kΩ
Shield *3
V+
250Ω
*5
I+
VI-
200kΩ
FG
*2
ch
:
represents the channel number.
*1 For FX
/FX
/FX5U PLC (AC power type), the 24V DC service power
3G
3U
supply is also available.
*2 The [FG] terminal and the [
] terminal are connected internally.
There is no "FG" terminal for ch1. When using ch1, connect directly to the
[
] terminal.
*3 Use a 2-core twisted shield wire for analog input line, and separate it from
other power lines or inductive lines.
*4 For the current input, short-circuit the [V+] terminal and the [I+] terminal.
*5 If there is voltage ripple in the input voltage or there is noise in the external
wiring, connect a capacitor of approximately 0.1 to 0.47µF 25 V.
3.4 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared
grounding" of the following figure.
→ For details, refer to the FX
Series User's Manual - Hardware Edition.
3G
→ For details, refer to the FX
3GC
Series User's Manual - Hardware Edition.
→ For details, refer to the FX
Series User's Manual - Hardware Edition.
3U
→ For details, refer to the FX
Series User's Manual - Hardware Edition.
3UC
→ For details, refer to the MELSEC iQ-F FX5U User's Manual (Hardware)
→ For details, refer to the MELSEC iQ-F FX5UC User's Manual (Hardware)
Another
Another
PLC
PLC
equipment
equipment
Independent grounding
Shared grounding
Best condition
Good condition
• The grounding wire size should be AWG 14 (2 mm
• The grounding point should be close to the PLC, and all grounding wire
should be as short as possible.
4. Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric representative.
• Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
• Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION AND
STORAGE PRECAUTIONS
• The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
+15V
boxes and shock-absorbing palettes.
-15V
Failure to do so may cause failures in the product.
After transportation, verify operation of the product and check for damage of the
mounting part, etc.
4.1 Applicable PLC
ch
Model name
Applicability
Ver. 1.00 or later (from first production)
FX
3G
Series PLC
Up to 8 blocks can be extended
Ver. 1.40 or later (from first production)
FX
Series PLC
*1
3GC
Up to 8 blocks can be extended
Ver. 2.20 or later (from first production)
FX
3U
Series PLC
ch
Up to 8 blocks can be extended
Ver. 1.30 or later (from the production manufactured in August,
FX
Series PLC
*1
2004 with SER No. 48
)
3UC
Up to 8 blocks can be extended
Ver. 1.000 or later (from first production)
FX5U PLC
*3
Up to 8 blocks can be extended
Ver. 1.000 or later (from first production)
FX5UC PLC
*3
Up to 8 blocks can be extended
The version number can be checked by monitoring D8001 as the last three digits
indicate it.
*1 An FX
-CNV-IF or FX
-1PS-5V is necessary to connect the FX
2NC
3UC
the FX
/FX
PLC.
3GC
3UC
*2 Up to 7 units can be connected to the FX
-32MT-LT(-2) PLC.
3UC
*3 An FX5-CNV-BUS or FX5-CNV-BUSC is necessary to connect the FX
with the FX5U/FX5UC PLC.
4.2 General Specifications
For the general specifications other than the following, refer to the manual of the PLC
main unit.
The items other than the following are equivalent to those of the PLC main unit.
→ For details, refer to the FX
3G
Series User's Manual - Hardware Edition.
→ For details, refer to the FX
Series User's Manual - Hardware Edition.
3GC
→ For details, refer to the FX
3U
Series User's Manual - Hardware Edition.
→ For details, refer to the FX
Series User's Manual - Hardware Edition.
3UC
→ For details, refer to the MELSEC iQ-F FX5U User's Manual (Hardware)
→ For details, refer to the MELSEC iQ-F FX5UC User's Manual (Hardware)
Item
Specification
Dielectric withstand
500V AC for one minute
voltage
5 M Ω o r h i g h e r b y 5 0 0 V D C
Insulation resistance
insulation resistance tester
4.3 Power Supply Specifications
Item
24V DC ±10%, 90mA
A/D conversion
circuit driving power
(24V DC power is supplied from the power connector.)
5V DC, 110mA
Another
PLC
CPU driving power
(5V DC power is supplied from the internal power supply of
equipment
main unit.)
4.4 Performance Specifications
Common grounding
Not allowed
2
).
Item
Voltage input
Analog input
-10 to +10V DC
range
(Input resistance: 200 kΩ)
*1
*2
Offset
-10 to +9V
*1
*2
Gain
-9 to +10V
Maximum
±15V
absolute input
Digital output
With sign, 16bits, binary
Resolution
0.32mV (20V/64000)
• ±0.3% (±60mV) for full scale
of 20V (when ambient
temperature is 25°C±5°C)
Total accuracy
• ±0.5% (±100mV) for full scale
of 20V (when ambient
temperature is 0°C to 55°C)
A/D conversion
(If channels use the digital filter(s): 5ms × number of selected
time
Input mode 0
Digital value
+32640
+32000
-10
Input
characteristics
*4
*2
-4AD with
3U
• The photo-coupler insulates the analog input area from the PLC.
-4AD
3U
• The DC-DC converter insulates the analog input area from the
Insulation
method
power supply unit.
• Channels are not insulated from each other.
Occupied
8 point (Count either the input or output points of the PLC.)
points
*1 Change the offset and gain values to change the input characteristics. However,
the resolution doesn't change even when the offset and gain values change.
When the analog value direct indication is enabled in the input mode 2, 5, or 8,
the offset value and the gain value don't change.
*2 The offset and the gain should satisfy the following condition:
1V ≤ (Gain - Offset) ≤ 7.5V
*3 The offset and the gain should satisfy the following condition:
3mA ≤ (Gain - Offset) ≤ 30mA
Between all terminals and
*4 The input characteristics vary depending on the input mode to be used.
ground terminal of PLC
For the details of the input characteristics, refer to the following manual.
main unit
→ Refer to the FX
4.5 Input characteristics
The input characteristics in each input mode are as follows.
Specification
For the details of the input characteristics, refer to the following manual.
Input
mode
0
1
Description
2
Current input
3
-20 to +20mA, 4 to 20mA DC
(Input resistance: 250Ω)
4
*3
-20 to +17mA
5
*3
-17 to +30mA
6
±30mA
7
With sign, 15bits, binary
8
1.25µA (40mA/32000)
• ±0.5% (±200µA) for full scale
of 40mA (when ambient
「电器电子产品有害物质限制使用标识要求」的表示方式
temperature is 25°C±5°C and
a current of -20 mA to +20 mA
is input)
Same when input is 4mA to
20mA
• ±1.0% (±400µA) for full scale
of 40mA (when ambient
含有有害6物质的名称, 含有量, 含有部品
temperature is 25°C±5°C and
  本产品中所含有的有害6 物质的名称, 含有量, 含有部品如下表
a current of -20 mA to +20 mA
所示。
is input)
Same when input is 4mA to
20mA
500µs × number of selected channels
channels)
部件名称
Input mode 3
Digital value
16400
可编程
控制器
16000
0
本表格依据SJ/T 11364的规定编制。
+10
Input
○ :表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
voltage(V)
0
4
20
规定的限量要求以下。
-32000
Input
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
-32640
current(mA)
26572规定的限量要求。
Input mode 6
Digital value
基于中国标准法的参考规格:GB/T15969.2
+16320
+16000
-20
This manual confers no industrial property rights or any rights of any other kind,
0
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
+20
held responsible for any problems involving industrial property rights which may
Input
occur as a result of using the contents noted in this manual.
current(mA)
-16000
Warranty
-16320
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
/FX
/FX
/FX
/FX
Series User's Manual
3S
3G
3GC
3U
3UC
product fails, install appropriate backup or failsafe functions in the system.
- Analog Control Edition
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
→ Refer to the FX
/FX
/FX
/FX
/FX
Series User's Manual
3S
3G
3GC
3U
3UC
- Analog Control Edition
Analog input
Digital output
Input mode
range
range
Voltage input mode
-10 to +10V
-32000 to +32000
Voltage input mode
-10 to +10V
-4000 to +4000
Voltage input mode
-10 to +10V
-10000 to +10000
Analog value direct indication
Current input mode
4 to 20mA
0 to 16000
Current input mode
4 to 20mA
0 to 4000
Current input mode
4 to 20mA
4000 to 20000
Analog value direct indication
Current input mode
-20 to +20mA
-16000 to +16000
Current input mode
-20 to +20mA
-4000 to +4000
Current input mode
-20 to +20mA
-20000 to +20000
Analog value direct indication