The following are the 51-n supported Curve Characteristic:
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-MI, ANSI-VI, ANSI-EI
Operating time for IEC :
Operating time for IEEE/ANSI :
Reset time for IEC/IEEE/ANSI
Table 3-2
Curve type
IEC-NI
0.14
IEC-VI
13.5
IEC-EI
80
IEC-LTI
120
IEEE/ANSI - MI
----
IEEE/ANSI - VI
----
IEEE/ANSI - EI
----
Where,
I - Fault current Magnitude
I
- Pickup setting
s
Tm - Time multiplier
Table 3-3
Parameters
Gn 51-n Element
51-1 Block
Gn 51-n Setting
Pick-up current
Gn 51-n Char
Characteristics
Gn 51-n Time Mult
Time Multiplier
(other than DTL)
Delay
Gn 51-n Delay
(Applicable only
for DTL)
Gn 51-n Min
Minimum Operate
Operate
Time
Gn 51-n Follower
Follower DTL
Gn 51-n Reset
Reset
©2018 Siemens Protection Devices Limited
K
α
t
=
I
op
( )
1
Is
A
P
t
=
I
op
( )
1
Is
R
t
=
I
r
( )
:
1
Is
Constants for operating and reset curve characteristics
Operating time
K
α
P
0.02
----
1.0
----
2.0
----
1.0
----
----
0.02
----
2.0
----
2.0
Time Delayed Overcurrent Protection (51-n)
Description
Default Value
Disabled
1xI
n
IEC NI
1
5 s
0 s
0 s
0 s
Chapter 1 - 7SR45 Description of Operation
X Tm
+ B
X Tm
n
X Tm
A
B
----
----
----
----
----
----
----
----
0.0515
0.114
19.61
0.491
28.2
0.1217
Min
Max
-
-
0.2xI
2.0xI
n
-
-
0.01 s
10
0 s
15 s
0 s
20 s
0 s
20 s
60, IEC/
0 s
ANSI
DECAY
Reset time
R
n
9.7
2
43.2
2
58.2
2
80
2
4.85
2
21.6
2
29.1
2
Step Change
-
0.01
n
-
0.01
0.01
0.01
0.01
1
Chapter 1 Page 26 of 48