INSTALLATION MANUAL AIR CONDITIONER
TYPE : WALL MOUNTED
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
• Do not cool excessively indoors. This may be harmful for your health and may consume more
electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air
conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer's name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak
performance of your product.
WARNING
!
It can result in serious injury or death when the directions are ignored.
CAUTION
!
It can result in minor injury or product damage when the directions are ignored.
WARNING
!
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Air conditioner Shall be installed in accordance with national wiring regulations.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similary qualified persons in order to avoid a hazard.
• The information contained in the manual is intended for use by a qualified service technician familiar
with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunc-
tion, property damage, personal injury and/or death.
Installation
• Always perform grounding.
- Otherwise, it may cause electrical shock.
• Don't use a power cord, a plug or a loose socket which is damaged.
- Otherwise, it may cause a fire or electrical shock.
• For installation of the product, always contact the service center or a professional installation
agency.
- Otherwise, it may cause a fire, electrical shock, explosion or injury.
• Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
- If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not
attached securely, it could result in a fire or electric shock due to dust, water, etc.
• Always install an air leakage breaker and a dedicated switching board.
- No installation may cause a fire and electrical shock.
• Do not keep or use flammable gases or combustibles near the air conditioner.
- Otherwise, it may cause a fire or the failure of product.
• Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.
- It may cause injury or an accident.
• Do not disassemble or repair the product randomly.
- It will cause a fire or electrical shock.
• Do not install the product at a place that ther is concern of falling down.
- Otherwise, it may result in personal injury.
• Use caution when unpacking and installing.
- Sharp edges may cause injury.
• Thickness of copper pipes used are as shown "Flaring work" Table.
- Never use copper pipes thinner than that in the table even when it is available on the market
• Do not use copper pipes having a collapsed.
Burrs removal
Handle
1. Completely remove all burrs from the cut
Bar
Bar
cross section of pipe/tube.
2. While removing burrs put the end of the
copper tube/pipe in a downward direction
while removing burrs location is also
changed in order to avoid dropping burrs
Copper pipe
into the tubing.
Clamp handle
Red arrow mark
Check
1
Compare the flared work with the figure
by.
2
If a flared section is defective, cut it off
and do flaring work again.
Putting nut on
Smooth all round
- Remove flare nuts attached to indoor and
Inside is shiny without scratches
outdoor unit, then put them on pipe/tube
having completed burr removal.
= Improper flaring =
(not possible to put them on after finishing
flare work)
Flare nut
Inclined
Surface
Cracked Uneven
damaged
thickness
Even length
all round
Copper tube
Connecting the Piping
1
Open the panel of the indoor unit.
2
Remove the chassis cover from the unit by
loosing 3 screws.
Flaring work
1
Firmly hold copper pipe in a bar with the di-
mension shown in the table below .
2
Carry out flaring work with the flaring tool.
Outside diameter
A
Thickness
mm
inch
mm
mm
Ø6.35
1/4"
1.1~1.3
0.7
Ø9.52
3/8"
1.5~1.7
0.8
Ø12.7
1/2"
1.6~1.8
0.8
Ø15.88
5/8"
1.6~1.8
1.0
Chassis cover
3
Pull back the tubing holder.
Bad case
4
Remove pipe port cover and positioning
- Following bending case from right to left di-
the tubing
rectly may cause damage to the tubing.
Tubing holder
Indoor unit back side view
Right
Left
Backwards
Downwards
* The feature can be changed according to a
type of model.
Good case
- Press on the tubing cover and unfold the
tubing to downward slowly. And then bend
to the left side slowly.
* The feature can be changed according to a
type of model.
!
CAUTION
Installation Information. For right piping.
Follow the instruction above.
- Before bending the tubing, set the conduit
like picture below by using the bracket and
black screws from accessory kit.
P/No : MFL67502112
- Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
• For R410A model, use piping, flare nut and tools which is specified for R410A refrigerant.
- Using of (R22) piping, flare nut and tools may cause abnormally high pressure in the refrigerant
cycle (piping), and possibly result in explosion and injury.
• It is desirable that the amount of residual oil less than 40 mg/10m.
Operation
• Do not share the outlet with other appliances.
- It will cause an electric shock or a fire due to heat generation.
• Do not use the damaged power cord.
- Otherwise, it may cause a fire or electrical shock.
• Do not modify or extend the power cord randomly.
- Otherwise, it may cause a fire or electrical shock.
• Take care so that the power cord may not be pulled during operation.
- Otherwise, it may cause a fire or electrical shock.
• Unplug the unit if strange sounds, smell, or smoke comes from it.
- Otherwise, it may cause electrical shock or a fire.
• Keep the flames away.
- Otherwise, it may cause a fire.
• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet
hands.
- Otherwise, it may cause a fire or electrical shock.
• Do not use the power cord near the heating tools.
- Otherwise, it may cause a fire and electrical shock.
• Do not open the suction inlet of the indoor/outdoor unit during operation.
- Otherwise, it may electrical shock and failure.
• Do not allow water to run into electrical parts.
- Otherwise, it may cause the failure of machine or electrical shock.
• Hold the plug by the head when taking it out.
- It may cause electric shock and damage.
• Never touch the metal parts of the unit when removing the filter.
- They are sharp and may cause injury.
• Do not step on the indoor/outdoor unit and do not put anything on it.
- It may cause an injury through dropping of the unit or falling down.
• Do not place a heavy object on the power cord.
- Otherwise, it may cause a fire or electrical shock.
• When the product is submerged into water, always contact the service center.
- Otherwise, it may cause a fire or electrical shock.
• Take care so that children may not step on the outdoor unit.
- Otherwise, children may be seriously injured due to falling down.
CAUTION
!
Installation
• Install the drain hose to ensure that drain can be securely done.
- Otherwise, it may cause water leakage.
• Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to
the neighbors.
- Otherwise, it may cause dispute with the neighbors.
• Always inspect gas leakage after the installation and repair of product.
- Otherwise, it may cause the failure of product.
• Keep level parallel in installing the product.
- Otherwise, it may cause vibration or water leakage.
Operation
• Avoid excessive cooling and perform ventilation sometimes.
- Otherwise, it may do harm to your health.
• Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.
- The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.
• Do not use an appliance for special purposes such as preserving animals vegetables, precision
machine, or art articles.
- Otherwise, it may damage your properties.
• Do not place obstacles around the flow inlet or outlet.
- Otherwise, it may cause the failure of appliance or an accident.
<Right side piping>
Installation of Indoor Unit
1
Hook the indoor unit onto the upper por-
tion of the installation plate.( engage the
Yoke
three hooks at the top of the indoor unit
with the upper edge of the installation
Cone
plate) Ensure that the hooks are properly
seated on the installation plate by moving
it left and right.
Cover
Installation plate
3
Secure the cable onto the control board
with the cable retainer.
2
Unlock the tubing holder from the chassis
4
Close the cover of control box.
and mount between the chassis and instal-
lation plate in order to separate the bottom
5
Tape the tubing pipe, drain hose and the
side of the indoor unit from the wall.
conduit. Be sure that the drain hose is lo-
cated at the lowest side of the bundle.
Locating at the upper side can cause over-
flow from the drain pan through the inside
of the unit.
<Left side piping>
Tubing Holder
* The feature can be changed according to a
type of model.
Piping
1
Raise the cover of terminal block.
2
Insert the connecting cable through the
bottom side of indoor unit and connect the
cable. (You can see detail contents in 'Con-
necting the cables' section.)
!
NOTE
<Left side piping>
Insert the drain hose at left side when
you use left side piping type.
<Right side piping>
View
Cover
Terminal block
Connecting cable
Cable retainer
* The feature can be changed according to a
type of model.
!
CAUTION
Must use the elbow type
(L-Type) conduit
Wrench
Method:
1. Disassemble bracket
Indoor unit tubing
(from indoor unit)
3. When needed to extend the drain hose of
2. Assemble it with conduit
indoor unit, assembly the drain pipe as
3. Reassemble it with
shown on the drawing
indoor unit..
!
CAUTION
Drain pipe
If the drain hose is routed inside the room
insulate the hose with an insulation mate-
rial* so that dripping from sweating (con-
densation) will not damage furniture or
floors.
* Foamed polyethylene or equivalent is
recommended.
Wrap the insulation material
around the connecting portion.
1
Overlap the connection pipe insulation ma-
terial and the indoor unit pipe insulation
material. Bind them together with vinyl
Connecting the installation pipe
tape so that there may be no gap.
and drain hose to the indoor unit.
1
Align the center of the pipes and suffi-
ciently tighten the flare nut by hand
Indoor unit tubing
Flare nut Pipes
2
Set the tubing cutting line upward.
Wrap the area which accommodates the
2
Tighten the flare nut with a wrench
rear piping housing section with vinyl tape.
Outside Diameter
Torque
mm
inch
kgf·cm
N·m
Ø6.35
1/4
180~250 17.6~24.5
Ø9.52
3/8
340~420 33.3~41.2
Ø12.7
1/2
550~660 53.9~64.7
Ø15.88
5/8
630~820 61.7~80.4
Gas Pipe
Good Case
* Tubing cutting line have to be upward.
4
ENGLISH
INSTALLATION PARTS
Name
Quantity
Installation plate
1 EA
The feature can be changed according to a type of model.
Type "A" screw
5 EA
Type "B" screw
2 EA
Type "C" screw
2 EA
2 EA
Type "D" screw
Bracket
1 EA
Remote control
1 EA
holder
Screws for fixing panels are attached to decoration panel.
INSTALLATION TOOLS
Figure
Name
Screw driver
Electric drill
Measuring tape, Knife
Hole core drill
Spanner
Torque wrench
INSTALLATION MAP
* The feature can be changed according to a type of model.
!
NOTE
• You should purchase the installation parts.
1
Indoor unit pipe
Connection pipe
Vinyl tape (wide)
Wrap with vinyl tape
Connecting cable
Pipe
View
Vinyl tape(narrow)
3
Bundle the piping and drain hose together
Terminal block
by wrapping them with vinyl tape sufficient
Connecting cable
enough to cover where they fit into the
Cable retainer
rear piping housing section.
Wrap with vinyl tape
Pipe
Vinyl tape(wide)
Drain hose
Finishing the indoor unit
installation
1
Mount the tubing holder in the original
positon.
2
Ensure that the hooks are properly seated
on the installation plate by moving it left
and right.
Drain hose
3
Press the lower left and right sides of the
unit against the installation plate until the
Tape
hooks engage into their slots (clicking
Conduit
sound).
4
Finish the assembly by screwing the unit
Drain hose
Connecting pipe
to the installation plate by using two pieces
of type "C" screws. And assemble a chas-
sis cover.
Tape
Conduit
Drain hose
Connecting pipe
Type 'C' screw
- Finally, tighten the flare nut with torque
Open-end wrench
wrench until the wrench clicks.
(fixed)
When tightening the flare nut with torque
wrench, ensure the direction for tightening
Flare nut
follows the arrow on the wrench.
Connection
pipe
Outdoor unit
Liquid side piping
(Smaller diameter)
Indoor unit drain hose
Vinyl tape(narrow)
Adhesive
Torque wrench
Gas side piping
(Bigger diameter)
Insulation material
Outside Diameter
Torque
mm
inch
kgf·cm
Ø6.35
1/4
180~250 17.6~24.5
Ø9.52
3/8
340~420 33.3~41.2
Ø12.7
1/2
550~660 53.9~64.7
Ø15.88
5/8
630~820 61.7~80.4
Cutting Line
Cutting Line
Liquid Pipe
Bad Case
5
INSTALLATION
Select the best Location
Shape
Indoor unit
- There should not be any heat or steam near
the unit.
- Select a place where there are no obstacles
around of the unit.
- Make sure that condensation drainage can
be conveniently routed away.
- Do not install near a doorway.
- Ensure that the gap between a wall and the
left (or right) of the unit is more than 4in. The
unit should be installed as high as possible
on the wall, allowing a minimum of 8in from
ceiling.
- Use a metal detector to locate studs to pre-
vent unnecessary damage to the wall.
More than
4
Figure
Name
Multi-meter
* Recommended height 6.5ft from the floor.
* The feature can be changed according to
the type of model.
Hexagonal wrench
!
CAUTION
Ammeter
Remove obstructions to prevent blockage
of airflow path.
Gas-leak detector
Thermometer,
Level
Flaring tool set
Indoor unit
Fixing Installation Plate
The wall you select should be strong and solid
enough to prevent vibration.
1
Before installation, confirm the position of
a screw between chassis and Installation
plate.
Installation plate
Sleeve
Bushing-Sleeve
Putty(Gum Type Sealant)
Bend the pipe as closely
on the wall as possible,
but be careful that it
doesn't break.
Vinyl tape (Wide)
• Apply after carrying out a
drainage test.
2
Mount the installation plate on the wall
• To carry out the drainage
with type "A" screws. If mounting the unit
test, remove the air filters
Saddle
and pour water into the heat
on a concrete wall, use anchor bolts.
exchanger.
- Mount the installation plate horizontally
by aligning the centerline using Horizontal
meter .
Installation Plate
Gas side piping
(Optional Parts)
Liquid side piping
(Optional Parts)
Additional drain pipe
Vinyl tape (Narrow)
Drain Hose
Connecting cable
(Optional Parts)
Chassis
Hook
3
Measure the wall and mark the centerline.
It is also important to use caution concern-
ing the location of the installation plate.
Routing of the wiring to power outlets is
through the walls typically. Drilling the hole
through the wall for piping connections
must be done safely.
2
!
CAUTION
!
CAUTION
• Before finishing installation of the indoor
The power cord connected to the outdoor
unit, seal the hole of a wall except the
unit should be complied with the follow-
pipe's ways to prevent condensate from
ing specifications(UL recognized or CAS
inflow of outdoor air.
certified)
Outdoor unit
Connecting the Piping
- Remove the tubing cover from the unit by
loosening the screw.
Power
"A"
Tubing cover
The power connecting cable connected to the
indoor and outdoor unit should be complied
with the following specifications (UL recog-
nized or CAS certified).
Power
- Align the center of the pipings and suffi-
ciently tighten the flare nut by hand.
"B"
* Field wiring shall be done such that the cur-
rentcarrying conductors become taut before
the earthing conductor if the cord slips out
of the cord anchorage.
Connecting the Cables
CAUTION
!
Connect the cable to the indoor unit by con-
According to the confirmation of the
necting the wires to the terminals on the con-
above conditions, prepare the wiring as
trol board individually according to the outdoor
follows.
unit connection. (Ensure that the color of the
wires of the outdoor unit and the terminal No.
1
Never fail to have an individual power
are the same as those of the indoor unit.)
circuit specifically for the air condi-
tioner. As for the method of wiring, be
guided by the circuit diagram posted
on the inside of control cover.
!
CAUTION
2
The screw which fasten the wiring in
the casing of electrical fittings are li-
- The circuit diagram is a subject to
able to come loose from vibrations to
change without notice.
which the unit is subjected during the
- The earth wire should be longer than the
course of transportation. Check them
common wires.
and make sure that they are all tightly
fastened. (If they are loose, it could
- When installing, refer to the circuit dia-
cause burn-out of the wires.)
gram on the chassis cover.
3
Specification of power source.
- Connect the wires firmly so that they
4
may not be pulled out easily.
Confirm that electrical capacity is suffi-
cient.
- Connect the wires according to color
5
codes, referring to the wiring diagram.
See that the starting voltage is main-
tained at more than 90 percent of the
rated voltage marked on the name
plate.
6
Confirm that the cable thickness is as
specified in the power source specifi-
cation.
(Particularly note the relation between
cable length and thickness.
7
Always install an earth leakage circuit
breaker in a wet or moist area.
8
The following would be caused by volt-
age drop.
- Vibration of a magnetic switch, which
N·m
will damage the contact point, fuse
breaking, disturbance of the normal
function of the overload.
9
The means for disconnection from a
power supply shall be incorporated in
the fixed wiring and have an air gap
contact separation of at least 3mm in
each active(phase) conductors.
6
Outdoor unit
- If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure
that heat radiation from the condenser is not
restricted.
- Ensure that the space around the back side
and other sides is more than 12in. The space
in front of the unit should be more than 28in.
- Do not place animals and plants in the path
of the warm air.
- Take the weight of the air conditioner into ac-
count and select a place where noise and vi-
bration are minimum.
- Select a place where the warm air and noise
from the air conditioner do not disturb neigh-
bors.
More than
12
More than 8
F e
n c e
o b
s t a
o r
More than
More than
c l e
12
s
4
More than
24
More than
28
(Unit : in)
(Unit : in)
Place a level on raised tab
Unit
A Type : 442
A Type : 442
Outline
B Type : 434
B Type : 439
Ø65
Ø65
Ø65
Ø65
Installation Plate
Installation Plate
A Type B Type
A Type : 133
A Type : 95
175
217
B Type : 123
B Type : 170
(Unit : mm)
Drill a Hole in the Wall
- Drill the piping hole with a ø65mm hole core
drill. Drill the piping hole at either the right or
the left with the hole slightly slanted to the
outdoor side.
WALL
A-Type
Indoor
Outdoor
B-Type
Flaring Work
Main cause for gas leakage is due to defect of
flaring work. Carry out correct flaring work in
the following procedure.
Cut the pipes and the cable
Type "A" Screws
1
Use the piping kit accessory or the pipes
purchased locally.
2
Measure the distance between the indoor
and the outdoor unit.
3
Cut the pipes a little longer than measured
distance.
4
Cut the cable 1.5m longer than the pipe
length.
Copper
pipe
90°
Slanted Uneven Rough
- Connect the wires to the terminals on the
control board individually.
- Secure the cable onto the control board with
the cord clamp.
- Use a recognized circuit breaker between
the power source and the unit.
A disconnecting device to adequately discon-
nect all supply lines must be fitted.
- Provide a circuit breaker between power
source and the outdoor unit as shown below.
AWG_"A"
Capacity(Btu/h)
Circuit
Breaker
9k~12k
(A)
15
Terminal block
Capacity(Btu/h)
Over 5mm
9k/12k
(0.2")
14
Connecting
cable
Power
supply
cord
AWG_"B"
Conduit panel
Tubing cover
!
CAUTION
When using the separate wire as the
Capacity(Btu/h)
power cord, please fix the separate wire
into the control box panel by using tie
9k/12k
wrap as the fixture. "A" & "B" are minimum
18
recommended wire size.
Main power source
Air
Circuit Breaker
Conditioner
Use a circuit breake
or time delay fuse.
Checking the Drainage
To check the drainage.
1
Pour a glass of water on the evaporator.
2
Ensure the water flows through the drain
hose of the indoor unit without any leak-
age and goes out the drain exit.
Connecting area
drain hose
Leakage
checking
Drain pan
Drain
hose
Leakage
checking
Drain piping
1
The drain hose should point downward for
easy drain flow.
Downward slope
3
7

Advertisement

loading

Summary of Contents for LG LA090HYV

  • Page 1 ENGLISH INSTALLATION PARTS INSTALLATION Select the best Location Outdoor unit Name Quantity Shape INSTALLATION MANUAL AIR CONDITIONER - If an awning is built over the unit to prevent Indoor unit direct sunlight or rain exposure, make sure that heat radiation from the condenser is not - There should not be any heat or steam near Installation plate 1 EA...