Omega DP20 Quick Installation Manual

Hide thumbs Also See for DP20:

Advertisement

Quick Links

DP20 shown smaller
than actual size
1. Front view
Alarm 1 and 2
Units
Key 'LE'
Key 'SQ'
1. Exit the menu
Key 'UP'
1. Enter into 'Fast access'
2. Next value
2. Dimensions and panel cut-out (mm)
Panel
48 mm
44
cut-out
(1.89)
(1.74)
92
(3.63)
96 mm
91 mm
(3.78)
(3.58)
(including terminal)
Detail of the female
terminal provided.
3. Additional documentation
To view the DP20 spec sheet and manuals visit us at https://www.omega.com/pptst/DP20.html
4. How to order
Model
Option 1
Option 2
DP20
-
-
-A1 (1 relay)
-A2 (1 relay)
-M1 (analog output)
-(empty)
-S1 (Modbus RTU)
-(empty)
Quick installation guide DP20 (page 1/2)
TM
5. Installation and start-up
1.
Open the instrument (see section 7).
2.
Select the jumpers for the desired signal range (see section 8).
3.
Close the instrument (see section 7).
4.
Connect the signal and the power (see section 6).
5.
Configure the instrument from the 'Configuration menu' (see section 9).
6.
If you need additional information, see section 3.
6. Connections
Option A2 (relay)
Option A1 (relay)
Com.
Com.
NO
NO
NC
NC
G
H
I
A B C
A B C
Option S1 (Modbus RTU)
Option 2
Option 1
A B C
G
H
I
A B C
1 2 3 4 5
8 9 0
+Vdc / Phase
Not Connected
-Vdc / Neutral
Vexc, Pt100 3 wires, pot+
external control
neutral, 0 V, common
5 Aac, ±5 Adc
~
Vac, ±Vdc, resistance, mA, pot
~
thermocouple+, Pt+, Ni+, PTC+, NTC+
600 Vac,
200 Vac
~
~
±600 Vdc, ±200 Vdc
Protection fuse value :
250 mA time-lag for power voltage > 50 Vac/dc
400 mA time-lag for power voltage < 50 Vac/dc
16
(0.63)
7. How to open the instrument
Use a flat screwdriver to unlock clips 'D', C', 'B'
and 'A', in this order. Remove the front filter.
75
(2.95)
Gently let the internal boards slide out of the
instrument.
To reinsert the boards in the housing :
8
(0.31)
1.
make sure that the boards are correctly con-
nected to the displays pins
2.
slide the boards into the housing guides
3.
place the front filter at corner X, and then
insert clips 'A', 'B', 'C' and 'D' in this order.
Risk of electric shock. Removing the front cover will grant access to internal
circuits which may be at dangerous voltage. Disconnect the input signal and
the power supply to prevent electric shock to the operator. Operation must be
performed by qualified personnel only.
8. Internal structure and jumpers for range selection
Front filter
!
Opt.1
Option M1 (4/20 mA)
Vexc.
(active output A-B)
4/20 mA
(passive output B-C)
Common
Internal Jumpers
B
A
Common
Displays
Jumpers 'S'
for signal range selection
K
J
I
H
G
F
E
D
C
B
A
Input signal terminal
AC ranges
Scalable
600 Vac
~ 
200 Vac
~ 
20 Vac
~ 
B
D
2 Vac
from 9999
~ 
to -1999
200 mVac
~ 
60 mVac
~ 
5 Aac
~ 
20 mAac
~ 
C
DC ranges
Scalable
X
A
±600 Vdc
±200 Vdc
±20 Vdc
±2 Vdc
from 9999
to -1999
±200 mVdc
±60 mVdc
±5 Adc
±20 mAdc
Resistance
Scalable
ranges
0 to 5 K
from 9999
to -1999
0 to50 K
Thermocouples Jumpers
Display module
Optional modules
Opt.1
Opt.2
Housing
Jumpers not used can be
K
stored in the following three
J
I
'no contact' positions.
H
G
F
E
D
C
B
A
1
Jumper 'T'
2
3
for terminal 5 function selection
4
5
6
Jumpers
Jumper
Accuracy
'S'
'T'
(% FS)
G I
Process
I
signals
A I
4/20 mA
<0.30 %
(up to 150 Hz)
B I
0/10 Vdc
4-5
* Place jumper 'T' at position 1-2 for +15 Vdc excitation voltage at terminal 5. Optionally,
C I
place jumper 'T' at position 4-5 to work with 'external contact' at terminal 5.
E I
Potentiometers
I
<0.50 %
nominal value
(up to 150 Hz)
D I
500 R to 20 K
Jumpers
Jumper
Accuracy
Frequency
'S'
'T'
(% FS)
G
15 Hz to 100 Hz
---
A
<0.20 %
PTC probes
B
Family
4-5
C
KTY-121
E
KTY-210
<0.25 %
- - -
KTY-220
D
<0.15 %
NTC probes 'R
'
Jumpers
Jumper
Accuracy
25
(configurable)*
'S'
'T'
(% reading)
10K
F H K
<1.5 % of
4-5
reading
*'Beta' configurable (2000 to 5500). R
F K
w w w.om ega. co m/ DP 20. htm l
Jumper
Range in ºC
Total error
'S'
'T'
(in ºF)
(cold junction included)
-100 / 1350 ºC
tc. K
(-148 / 2462 ºF)
-100 / 1200 ºC
tc. J
(-148 / 2192 ºF)
-100 / 1000 ºC
tc. E
E
(-148 / 1832 ºF)
-100 / 1300 ºC
tc. N
(-148 / 2372 ºF)
<3 º 
-100 / 900 ºC
tc. L
(-148 / 1652 ºF)
4-5
0 / 1768 ºC
tc. R
(32 / 3214 ºF)
0 / 1768 ºC
tc. S
E J
(32 / 3214 ºF)
-100 / 400 ºC
tc. T
(-148 / 752 ºF)
0 / 2300 ºC
tc. C
E
(32 / 4172 ºF)
<5 º
700 / 1820 ºC
tc. B
E J
(1292 / 3308 ºF)
Pt and Ni
Jumpers
Jumper
Range in ºC
Total
Current at
probes
'S'
'T'
(in ºF)
error
sensor
Pt100
-200 / 700 ºC
F H J
5-6
< 900 uA
(3 wires)
(-328 / 1292 ºF)
Pt100
-200 / 700 ºC
F H
< 900 uA
(2 wires)
(-328 / 1292 ºF)
-150 / 630 ºC
Pt500
F
< 90 uA
(-238 / 1166 ºF)
-190 / 630 ºC
Pt1000
F
<1º
< 90 uA
(-310 / 1166 ºF)
4-5
-60 / 180 ºC
Ni100
F H
< 900 uA
(-76 / 356 ºF)
-60 / 120 ºC
Ni200
F H
< 900 uA
(-76 / 248 ºF)
-60 / 180 ºC
Ni1000
F
< 90 uA
(-76 / 356 ºF)
Scalable
Jumpers
Jumper
Accuracy
'S'
'T'
(% FS)
D
<0.15 %
from 9999
1-2
*
to -1999
A
<0.20 %
Scalable
Jumpers
Jumper
Accuracy
'S'
'T'
(% FS)
from 9999
A
2-3
<0.5 %
to -1999
Scalable
Jumpers 'S'
Jumpers 'T'
Accuracy
(% of reading)
from 9999
select Vac or
4-5
<0.15%
to -1999
Aac range
of reading
Jumpers
Jumper
Range in ºC
Total error
'S'
'T'
(in ºF)
F
-55 / 150 ºC
F H K
4-5
<1 º
(-67 / 302 ºF)
F H K
Jumpers
Jumper
Range
Accuracy
Beta
'S'
'T'
of measure
(% of reading)
(configurable)
-60ºC to
<1.5 % of
F K
4-5
3500
reading
150ºC
configurable. Resistance measure from 100R to 1MR.
25
MQS5802_0618