Omega DP41-E Quick Start

High performance process indicator

Advertisement

Quick Links

5
Dec pt
Set Default Decimal Point
1. Press MENU. The meter displays:
SETPTS
/MAX
/MIN
2. Press
/MIN to display the current
FFFFFF.
decimal point. Change the display, if
necessary, to read "FFFFFF." (Use
/MAX to change the decimal point
SETPTS
/MAX
/MIN
position).
3. Press MENU. The meter stores changes (if applicable),
then displays "CNT BY".
stored
CNTBY
SETPTS
/MAX
/MIN
MENU
RESET
SETPTS
/MAX
/MIN
4. Press RESET twice. The meter momentarily displays
"RESET 2" then returns to the run mode. The meter
will now read the input signal (4mA = ≈ 000000.
and 20mA = ≈ 020000.).
Measure and Record Input Values
INPUT1
1. Apply 4mA to the input and record the
display reading.
SETPTS
/MAX
/MIN
INPUT 1 = _________________
Refer to this as Input One.
INPUT2
2. Apply 20mA to the input and record the
display reading.
INPUT 2 = _________________
SETPTS
/MAX
/MIN
Refer to this as Input Two.
3. Press MENU until the meter displays:
IN CNF
SETPTS
/MAX
/MIN
4. Press MENU until the meter displays:
INp6=0
Press
/MIN to display "INP6=0"
Change the meter to read "INP.6=1"
(Use
/MIN to scroll through digits
SETPTS
/MAX
/MIN
and
/MAX to change the digit's value).
5. Press MENU. The meter stores changes and displays:
stored
IN. S C. O F
SETPTS
/MAX
/MIN
MENU
RESET
SETPTS
/MAX
/MIN
MENU
RESET
6
Scale Input Values
1. Press
/MIN to display "INPUT 1":
MENU
RESET
Press
/MIN again. The meter
displays "000000". Enter the INPUT 1
value recorded in step 1 of the Measure
Input Values section of this quick start.
MENU
RESET
2. Press MENU. The meter displays
"READ 1":
Press
/MIN to display a six-digit
number. Change the meter to read
"000000". (Use
/MIN to scroll
through digits and
/MAX to change
the digit's value.)
MENU
RESET
3. Press MENU. The meter displays
"INPUT 2":
Press
/MIN. The meter displays
"000000". Enter the INPUT 2 value
recorded in step 2 of the Measure Input
Values section of this quick start.
4. Press MENU. The meter displays
"READ 2":
Press
/MIN to display a six digit
number. Change the meter to read
MENU
RESET
"001000". (Use
/MIN to scroll through
digits and
/MAX to change the digit's value.)
5. Press MENU. The meter stores changes and displays:
stored
MENU
RESET
SETPTS
/MAX
/MIN
MENU
RESET
6. Press
/MIN to display the current decimal point. Press
MENU
RESET
/MAX to change the decimal point location to "FFFFF.F".
7. Press MENU. The meter stores this change, then displays
"CNT BY"
stored
MENU
RESET
SETPTS
/MAX
/MIN
MENU
RESET
8. Press RESET twice. The meter displays:
"RESET 2", then returns to the run
mode. The meter is now scaled to
read 0 to 100.0 for a 4-20 mA input.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and
workmanship for a period of one (1) year from the date of purchase. In addition to OMEGA's
standard warranty period, OMEGA Engineering will extend the warranty period for four (4)
additional years if the warranty card enclosed with each instrument is returned to OMEGA.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA's Customer
Service Department will issue an Authorized Return (AR) number immediately upon phone or
INPUT1
written request. Upon examination by OMEGA, if the unit is found to be defective, it will be
repaired or replaced at no charge. OMEGA's WARRANTY does not apply to defects resulting
from any action of the purchaser, including but not limited to mishandling, improper
interfacing, operation outside of design limits, improper repair, or unauthorized modification.
This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows
SETPTS
/MAX
/MIN
MENU
RESET
evidence of having been damaged as a result of excessive corrosion; or current, heat,
moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGA's control. Components which wear are not warranted, including
but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes
READ 1
liability for any damages that result from the use of its products in accordance with
information provided by OMEGA, either verbal or written. OMEGA warrants only that
the parts manufactured by it will be as specified and free of defects. OMEGA MAKES
NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER,
EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES
SETPTS
/MAX
/MIN
MENU
RESET
INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The
remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA
with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the
component upon which liability is based. In no event shall OMEGA be liable for
consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used:
(1) as a "Basic Component" under 10 CFR 21 (NRC), used in or with any nuclear installation
or activity; or (2) in medical applications or used on humans. Should any Product(s) be used
INPUT2
in or with any nuclear installation or activity, medical application, used on humans, or misused
in any way, OMEGA assumes no responsibility as set forth in our basic
WARRANTY /DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and
hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the
SETPTS
/MAX
/MIN
MENU
RESET
Product(s) in such a manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department.
BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN
AUTHORIZED RETURN (AR) NUMBER FROM OMEGA'S CUSTOMER SERVICE
DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number
should then be marked on the outside of the return package and on any correspondence.
READ 2
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to
prevent breakage in transit.
SETPTS
/MAX
/MIN
MENU
RESET
FOR WARRANTY RETURNS, please have
the following information available BEFORE
contacting OMEGA:
1. P.O. number under which the product
was PURCHASED,
2. Model and serial number of the product
under warranty, and
3. Repair instructions and/or specific
problems relative to the product.
OMEGA's policy is to make running changes, not model changes, whenever an improvement is
possible. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
Dec pt
© Copyright 2002 OMEGA ENGINEERING, INC. All rights reserved.
This document may not be copied, photocopied, reproduced, translated, or reduced to any
electronic medium or machine-readable form, in whole or in part, without prior written consent
of OMEGA ENGINEERING, INC.
SETPTS
/MAX
/MIN
MENU
RESET
PATENT NOTICE: This product is covered by one or more of the following patents: U.S.
Pat. No. Des. 336,895; 5,274,577 / CANADA 2052599; 2052600 / ITALY 1249456;
1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150; 2048066 / UK PATENT
No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. The "Meter Case Bezel
Design" is a trademark of NEWPORT Electronics, Inc., registered in the U.S. USED
UNDER LICENSE. OTHER INTERNATIONAL PATENTS PENDING.
WARNING: These products are not designed for use in, and should not be used for, patient
connected applications.
This device is marked with the international caution symbol. It is important to read the
CNTBY
Setup Guide before installing or commissioning this device as it contains important
information relating to safety and EMC.
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach
SETPTS
/MAX
/MIN
MENU
RESET
Directives.
The information contained in this document is believed to be correct, but OMEGA Engineering,
Inc. accepts no liability for any errors it contains, and reserves the right to alter specifications
without notice.
REset2
,
TRADEMARK NOTICE:
®
omega.com
Engineering, Inc.
SETPTS
/MAX
/MIN
MENU
RESET
12450ML-99 Rev.G
OMEGAnet
www.omega.com
FOR NON-WARRANTY REPAIRS, consult
OMEGA for current repair charges. Have the
following information available BEFORE
contacting OMEGA:
1. P.O. number to cover the COST of the
USA:
repair,
ISO 9001 Certified
2. Model and serial number of product, and
3. Repair instructions and/or specific
problems relative to the product.
Canada:
For immediate technical or application assistance:
USA and Canada:
Mexico and
Latin American:
Benelux:
Czech Republic:
France:
®
,
®
are trademarks of OMEGA
Germany/Austria:
MQS1297/0807
DP41-E
High Performance
Process Indicator
®
®
®
On-Line Service
Internet e-mail
info@omega.com
Servicing North America:
One Omega Drive, P.O. Box 4047
Stamford CT 06907-0047
TEL: (203) 359-1660
FAX: (203) 359-7700
e-mail: info@omega.com
976 Bergar
Laval (Quebec) H7L 5A1
TEL: (514) 856-6928
FAX: (514) 856-6886
e-mail: info@omega.ca
Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
®
Customer Service: 1-800-622-2378 / 1-800-622-BEST
®
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
®
TEL: (001) 203-359-7803
FAX: (001) 203-359-7807
e-mail: espanol@omega.com
Servicing Europe:
TEL: +31 20 3472121
FAX: +31 20 6434643
Toll Free in Benelux: 0800 0993344
e-mail: sales@omegaeng.nl
Frystatska 184, 733 01 Karviná
TEL: +420 59 6311899
FAX: +420 59 6311114
e-mail: info@omegashop.cz
TEL: +33 1 61 37 29 00
FAX: +33 1 30 57 54 27
Toll Free in France: 0800 466 342
e-mail: sales@omega.fr
Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
TEL: +49 7056 9398-0
F AX: +49 7056 9398-29
Toll Free in Germany: 0800 639 7678
e-mail: info@omega.de

Advertisement

loading

Summary of Contents for Omega DP41-E

  • Page 1 WARRANTY/DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year from the date of purchase. In addition to OMEGA’s Dec pt standard warranty period, OMEGA Engineering will extend the warranty period for four (4) additional years if the warranty card enclosed with each instrument is returned to OMEGA.
  • Page 2 Manual as well as free Software are available at Wiring Example: Current Input with Sensor Excitation www.omega.com or on the CD-ROM Select Input Range enclosed with your shipment. 2. Press MENU. The meter stores changes (if applicable) 1.