Troubleshooting (continued)
Problem
Heat-on time too short.
Heat-on time too long.
No cooling.
1
1
Not applicable on heating-only model.
Check
— anticipator setting. (See Fig. 6 for
anticipator location.)
— anticipator setting. (See Fig. 6 for
anticipator location.)
— system switch. May be in OFF or
HEAT position.
— fuse or circuit breaker.
— condenser switch position.
Located outdoors and may be
turned Off.
— Y, G, RC thermostat connections.
Increase anticipator setting by 0.05.
Observe heating system operation.
Decrease anticipator setting by 0.05.
Observe heating system operation.
Move switch to COOL position.
If fuse is blown or breaker tripped,
replace or reset.
Move to ON position.
Turn Off power to cooling system. Check
for correct terminal hookups. Repair any
frayed or broken wires. Firmly tighten all
terminal screws.
20
Action
(continued)
69-0395—2