<How to remove the drain hose>
•
The drain hose can be removed by removing the
screw securing the drain hose and then pulling out
the drain hose.
•
When removing the drain hose, be careful of any
sharp edges of steel plate. The edges can injuries.
To install the drain hose, insert the drain hose firmly
•
until the connection part contacts with heat insulator,
and the secure it with original screw.
Drain hose
Fig. 10-3-11
<How to fix the Drain Cap>
1) Insert hexagon wrench (4 mm) in a center head.
4 mm
Fig. 10-3-12
2) Firmly insert drain cap.
No gap
Insert a hexagon
wrench (4 mm)
Fig. 10-3-13
CAUTION
Firmly insert the drain hose and drain cap;
otherwise, water may leak.
Do not apply lubricating oil
(refrigerant machine oil) when
inserting the drain cap. Application
causes deterioration and drain
leakage of the plug.
<In case of right or left piping>
• After scribing slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
Slit
<In case of bottom right or bottom left piping>
• After scribing slits of the front panel with a knife or
a making-off pin, cut them with a pair of nippers or
an equivalent tool.
Slit
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm
above the wall surface . If the connectin g pipe is laid
exceeding 43 mm abo ve the wall surface, the indoor
unit may unstably be set on th e wall. When bending the
connecting pipe, make sure to use a spring bender so
as not to crush the pipe .
Bend the connectio n pipe within a radius of 30 mm.
To connect the pipe after insta llation of the unit (figure)
520 mm
420 mm
R 30 mm (Use polisin (polyethylene)
core or the like for bending pipe.)
- 65 -
FILE NO. SVM-17001
Fig. 10-3-14
(To the forefront of flare)
Gas side
Liquid side
Outward form of indoor unit
Use the handle of screwdriver, etc.
Fig. 10-3-16