Message Supervision; Line Supervision; Emergency Microphone; Mains Power Supervision - Bosch Plena LBB1990/00 System Manual

Voice alarm system
Hide thumbs Also See for Plena LBB1990/00:
Table of Contents

Advertisement

Plena Voice Alarm System | Basic System Manual | Configuration
4.5.4

Message supervision

If supervision is enabled (see section 4.5.1), the internal
message manager of the voice alarm controller is
supervised. This message supervision consists of
supervision of the wave player using a check-sum and
supervision of the audio path using a pilot tone.
4.5.5

Line supervision

4.5.5. 1
Introduction
If supervision is enabled (see section 4.5.1), all
loudspeaker lines are supervised. Line supervision
consists of:
Short-circuit supervision (see section 4.5.5.2).
Impedance supervision (see section 4.5.5.3).
Short-to-ground supervision (see section 4.5.5.4).
4.5.5.2
Short-circuit supervision
The voice alarm controller continuously monitors all
loudspeaker lines in the system for short-circuits. If a
short-circuit is detected, the line output of the
short-circuited line is isolated and shut down within 200
ms. The system will remain operational. If the line is
dual-redundant connected (A and B) the short-circuited
line remains operational as well.
4.5.5.3
Impedance supervision
If supervision is enabled, the voice alarm controller
measures the impedance of all loudspeaker lines once
every 90 seconds. The reference values for impedance
supervision are stored in the voice alarm controller
during the system calibration (see section 5.3). If a
difference of > 15% is detected between the measured
line impedance and its reference value, the line is
considered faulty.
Note
For a correct impedance supervision, connect
loudspeakers as described in section 3. 1 0.
4.5.5.4
Short-to-ground supervision
If supervision is enabled, the voice alarm controller
continuously monitors all loudspeaker lines in the
system for short-to-ground situations. If a leakage
current > 30 + 15 mA is detected in a line, the line is
considered faulty.
Bosch Security Systems | 2005-04 | 9922 141 10364en
4.5.6

Emergency microphone

If supervision is enabled (see section 4.5.1), the audio
path and the PTT switch of the emergency microphone
are monitored from the capsule to the connection with
the voice alarm controller.
4.5.7

Mains power supervision

If supervision is enabled (see section 4.5.1), the
availability of the mains power is supervised.
4.5.8

Battery supervision

If supervision is enabled (see section 4.5.1), the
availability of the back-up power is supervised.
4.5.9
Internal power amplifier
supervision
If supervision is enabled, the internal power amplifier of
the voice alarm controller is supervised. The function of
this power amplifier depends on the position of the 2ch
operation switch (see section 4.5.11).
table 4.3: Internal power amplifier functions
Operational mode
1-channel
2-channel
4.5.10 External power amplifier
supervision
If supervision is enabled and the 2ch operation switch
(see section 4.5.11) is in the ON position, the external
power amplifier is supervised. In 2-channel mode, the
external power amplifier is always the call power
amplifier.
en | 29
Function
BGM/Call power amplifier
BGM/Spare power amplifier

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Plena lbb1956/00

Table of Contents