Setting an indoor unit installation option (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. The panel(display ) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air conditioner.
- The default setting of an indoor unit installation option is "02000-100000-200000-300000".
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is
more than one indoor unit.
- No need to assign SEG3, 6, 9, 10, 11, 16, 21, 22, 23, 24 which are non applicable. Even though those segments are set,
they will be ignored.
- If you set the applicable segments with numbers other than the indiciated, the initial setting will be maintained.
4. Set the indoor unit option by wireless remote controller.
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
Explanation
PAGE
Indication
Details
Indication
and Details
0
Option
SEG7
Explanation
PAGE
Indication
Details
Indication
and Details
1
Option
SEG13
Explanation
PAGE
Indication
Details
Indication
and Details
2
Samsung Electronics
SEG2
SEG3
MODE
Indication
Details
RESERVED
2
SEG8
SEG9
Use of drain pump
Indication
Details
0
Disuse
RESERVED
1
Use
Use +
2
3minute
delay
SEG14
SEG15
Setting the output of
Use of external control
external control
Indication
Details
Indication
0
Disuse
0
ON/OFF
1
Control
2
OFF Control
1
WINDOW
3
Control
SEG4
Use of external
temperature sensor
Indication
Details
0
Disuse
1
Use
SEG10
RESERVED
SEG16
S-Plasma ion
Details
Indication
Details
Thermo on
0
Disuse
Operation
1
Use
on
SEG5
Use of central control
Indication
Details
RESERVED
0
Disuse
1
Use
SEG11
Master / Slave
Indication
0
RESERVED
1
SEG17
Number of hours using
Buzzer control
Indication
Details
Indication
2
0
Use
6
1
Disuse
SEG6
SEG12
Details
slave
master
SEG18
filter
Details
1000 Hour
2000 Hour
4-5