Step 1: Mount the transmitter

Liquid applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the drain/vent valves are oriented upward.
Figure 2. Liquid applications
A
A. Coplanar
B. Inline
Gas applications
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Figure 3. Gas applications
B
A
A. Coplanar
B. Inline
Steam applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
Figure 4. Steam applications
A
A. Coplanar
B. Inline
4
B
B
May 2013