Settings; Rf Sensitivity - ABB RTU560 Operation Manual

Connections and settings
Table of Contents

Advertisement

RTU560
Connections and Settings
Communication Unit 560CMD11

Settings

Hardware settings and operation of the communi-
cation Interfaces of the 560CMD11 are carried out
with the RTUtil560 configuration tool. For the con-
figuration procedure of the communication Inter-
faces and the IO-Bus, please refer to the
560RTUtil user guide.
The following parameters have to be defined for
all protocols:
Baudrate:
dem control:
Direct link (TxD/RxD only)
WT link full duplex (560FSM10/11 no
handshake)
WT link half duplex (560FSM10/11 with
RTS / DCD)
Dial up (external modem without hand-
shake, without RTS / CTS)
Loop switch unit (RP570/71 Host Inter-
face only)
Link with collision avoidance (TxD, RxD,
DCD, without handshake (DNP 3.0 only)
The settings of the Ethernet Interface are:
Node name
IP address
Subnet mask
Default gateway
Routing information
The number of the host Interface.
Fig. 6: 560ANA02
Doc.-No.: 1KGT 150 765 V005 1
50 to 19 200 baud Mo-
For the configuration procedure of the GPRS-
Modem (only R0011), please refer to the function
description part 6.
The settings of the GPRS-Modem are:
Local IP address
Remote network IP address
PIN number SIM-Card
Username
User password
Provider Connectionstring (APN)
RF sensitivity (only R0011)
Main parameters for the transmitter
are:
 Max. output power: 30dBm ± 5dB
 Min. output power: 0dBm ±5dB
min. signal level at input of GPRS-
Chip: -108dBm
cable RG58 with losses of 0,546dB/m
≙ 10,92dB (20m)
antenna with a gain of 2,2dBi
Exemplary calculation:
min. signal (receive) with 20m cable =
-109dB + 10,92dB – 2,2dBr =
-99,28dBm
result: the RF signal at the point of
antenna shall be min. -99,28dBm